A Case Study on Pressurization Method using HVAC System depends on Outdoor Conditions to Reduce Stack Effect in the High-rise Office Building

초고층 사무소 건물 연돌효과 저감을 위한 외기온별 공조가압방안의 적용 사례연구

  • 조정훈 (서브원 FM사업부 FM 연구소) ;
  • 유정연 (한양대학교 대학원 건축환경시스템연구실) ;
  • 정연기 (서브원 FM사업부 FM 연구소) ;
  • 김기창 (서브원 FM사업부 자산사업담당) ;
  • 조동우 (한국건설기술연구원)
  • Received : 2015.08.27
  • Accepted : 2015.11.13
  • Published : 2015.11.30

Abstract

This study aims to investigate optimized mechanical pressurization of each outdoor air temperature in order to resolve noise problems associated with stack effect. For this study, noise levels resulted by stack effect was measured during three months of winter, and airtight practices and mechanical pressurization practices of each outdoor air condition employed on a high-rise office building under operation. Noise level was measured in the elevator halls located on the lobby floor(1st floor) and the highest floor (47th floor). The average noise level of the 1st floor was 59 dB(A) under all HVAC system-off, exceeding the recommended level 57 dB(A), even after average of 9dB(A) was reduced after airtight practices were employed, After mechanical pressurization practices as pressurized floor in high-rise zone were employed, most noise levels met the recommended niose level 57 dB(A) for 1F elevator lobby and 48 dB(A) for 47F elevator lobby.

Keywords

References

  1. Beranek, L. (2006). Noise and Vibration Control Engineering : Principles and applications. Willy.
  2. Kang, T., Kim, J., & Song, D. (2013). An analysis of the building designers and construction engineers understanding about stack effect, Journal of AIK(Planing & Design), 29(10), 249-57.
  3. Kim, J., Yu, J., Cho, D., Park, J., & Song, K. (2014). Research on HVAC system operating schemes for pressurization to reduce stack effect problems in elevator halls of high-rise office building. Journal of AIK(Planing & Design), 30(6), 239-46.
  4. Jo, J., Lim, J., Song, S., Yeo, M., & Kim, K. (2002). A case study on the field measurement and reduction of the stack effect in high-rise buildings, Journal of the Architectural Institute of Korea(AIK)(Planing & Design), 18(7), 169-76.
  5. Tamblyn, R. (1991). Coping with air pressure problems in tall buildings. ASHRAE Transactions, 97(1), 824-82.