DOI QR코드

DOI QR Code

A Study on Partial Discharge Degradation Properties of PVC Cable due to NaCl

NaCl에 의한 PVC 케이블의 부분방전 열화 특성에 관한 연구

  • Lee, Sung Ill (Department of Safety Engineering, Korea National University of Transportation)
  • 이성일 (한국교통대학교 안전공학과)
  • Received : 2015.09.19
  • Accepted : 2015.09.24
  • Published : 2015.10.01

Abstract

In this study, the partial discharge degradation properties for 2-core PVC cable($2cores{\times}1.5mm^2$ cross section, length of 10 cm, 20 cm, 30 cm) following immersion with the salt water that the 2%, 4%, 8% of NaCl is dissolved in 100 g of distilled water for 48 and 96 hours has been measured. The results of this study are as follows. When the degradation time in salt water of 2% NaCl is 48 hours, it found that the number of partial discharge increased as about 40 pps, 50 pps, 90 pps with increasing the length of cable to 10 cm, 20 cm, 30 cm. In case the concentration and degradation time is same, the inception and extinction voltage decreased with increasing the length of cable. When the degradation time in salt water is 96 hours and the length of cable is 20 cm, it found that the number of partial discharge decreased as 3,000 pps, 500 pps, 100 pps with increasing the concentration of NaCl to 2%, 4%, 8%.

Keywords

References

  1. S. I. Lee, KIEE, Smart High Power and Application, 1, 863 (2015).
  2. S. I. Lee, J. Korean Inst. Electr. Electron. Mater. Eng., 8, 522 (2014).
  3. S. I. Lee, J. Korean Inst. Electr. Electron. Mater. Eng., 9, 576 (2014).
  4. S. I. Lee, J. Korean Inst. Electr. Electron. Mater. Eng., 11, 730 (2014).
  5. S. I. Lee, J. Korean Inst. Electr. Electron. Mater. Eng., 12, 841 (2014).
  6. H. G. Cho and Y. K. Park, J. Korean Inst. Electr. Electron. Mater. Eng., 10, 770 (1997).
  7. J. J. Park and J. Y. Lee, IEEE Transactions on Dielectrics and Electrical Insulation, 17, 5 (2010). https://doi.org/10.1109/TDEI.2010.5411996