DOI QR코드

DOI QR Code

Evaluation of Drinking Water Treatment Efficiency according to Regeneration Temperatures of Granular Activated Carbon (GAC)

입상활성탄 재생온도에 따른 정수처리 효율 평가

  • 김상구 (부산광역시 상수도사업본부 수질연구소) ;
  • 손희종 (부산광역시 상수도사업본부 수질연구소) ;
  • 정종문 (부산광역시 상수도사업본부 수질연구소) ;
  • 류동춘 (부산광역시 상수도사업본부 수질연구소) ;
  • 유평종 (부산광역시 상수도사업본부 수질연구소)
  • Received : 2015.07.20
  • Accepted : 2015.09.09
  • Published : 2015.09.30

Abstract

This study carried out continuous column test for estimating the regeneration efficiency with regeneration times and temperatures. More times regenerated granular activated carbon (GAC) has more ash in the GAC and has less apparent density. Two times regenerated GAC ($2^{nd}$ re-GAC) could removed the Trihalomethanes (THMs) in the water for the first two week after starting continuous column test, on the other hand five times regenerated GAC ($5^{th}$ re-GAC) did not have adsorption capacity. The THMs concentration in the effluent was almost equal or higher than that of influent at the first time of continuous column test. $2^{nd}$ re-GAC showed much more DOC adsorption capacity than $5^{th}$ re-GAC and the GAC which was regenerated with $700^{\circ}C$ had highest DOC removal efficiency among the GACs with 600, 700, 800, $900^{\circ}C$ regeneration temperatures. It is anticipated the cost of GAC regeneration could be saved more 100 million won by reducing the furnace temperature of 3rd~4th and 5th~6th about $150^{\circ}C$ compared to the current regeneration condition.

Keywords

References

  1. Cannon, F. S., Snoeyink, V. L., Lee, R. G., Dagois, G., DeWolfe, J. R., 1993, Effect of calcium in field-spent GACs on pore development during regeneration, J. Am. Water Works Assoc., 85(3), 76-89. https://doi.org/10.1002/j.1551-8833.1993.tb05959.x
  2. Dabrowski, P., Podkoscielny, P., Hubicki, Z., Barczak, M., 2005, Adsorption of phenolic compounds by activated carbon-a critical review, Chemosphere, 58, 1049-1070. https://doi.org/10.1016/j.chemosphere.2004.09.067
  3. Ebie, K., Li, F., Azuma, Y., Yuasa, A., Hagishita, T., 2001, Pore distribution effect of activated carbon in adsorbing organic micropollutants from natural water, Water Res., 35(1), 167-179. https://doi.org/10.1016/S0043-1354(00)00257-8
  4. Moore, B. C., Cannon, F. S., Westrick, J. A., Metz, D. H., Shrive, C. A., DeMarco, J., Hartman, D. J., 2001, Changes in GAC pore structure during full-scale water treatment at Cincinnati: a comparison between virgin and thermally reactivated GAC, Carbon, 39, 789-807. https://doi.org/10.1016/S0008-6223(00)00097-X
  5. Narbaitz, R. M., McEwen, J., 2012, Electrochemical regeneration of field spent GAC from two water treatment plants, Water Res., 46, 4852-4860. https://doi.org/10.1016/j.watres.2012.05.046
  6. Roh, J. S., Son, H. J., Park, E. J., Hwang, Y. D., Shin, P. S., Kang, L. S., Joo, G. J., 2002, Changes in characteristics of natural organic matter and DBPs precursor removal by advanced water treatment processes, J. Kor. Soc. Environ. Eng., 24(12), 2075-2087.
  7. Son, H. J., Choi, J. T., Son, H. S., Lee, S. J., 2012, Analysis of attached bacterial communities of biological activated carbon process using DGGE method, J. Kor. Soc. Environ. Eng., 34(8), 533-540. https://doi.org/10.4491/KSEE.2012.34.8.533
  8. Son, H. J., Roh, J. S., Kim, S. G., Bae, S. M., Kang, L. S., 2005, Removal characteristics of chlorination disinfection by-products by activated carbon, J. Kor. Soc. Environ. Eng., 27(7), 762-770.
  9. Son, H. J., Ryu, D. C., Jang, S. H., 2010, Effect of pore structure change on the adsorption of NOM and THMs in water due to the increase of reactivation number of coal-based activated carbon, J. Kor. Soc. Environ. Eng., 32(10), 965-972.
  10. Waer, M. A., Snoeyink, V. L., Mallon, K. L., 1992, Thermal regeneration of activated carbon for the treatment of drinking water: time and temperature dependence, J. Am. Water Works Assoc., 84(3), 82-91.