Study on Seismic Fragility Analysis of Water Supply Facilities

상수도 시설물의 지진 취약도

  • Lee, Changsoo (Department of Civil Engineering, University of Seoul) ;
  • Shin, Deasub (Department of Civil Engineering, University of Seoul) ;
  • Lee, Hodam (Department of Civil Engineering, University of Seoul)
  • Received : 2015.02.09
  • Accepted : 2015.03.19
  • Published : 2015.03.31

Abstract

In this study, The failure of water supply facilities is categorized into two phases: functional failure and complete collapse. The fragility curve of water supply facilities under PGA has been developed for two loading cases: actual overseas earthquake and Korean artificial earthquake. The seismic fragility of water supply facilities has been analyzed and compared about failure phases and PGA. From the analysis results, the probability of failure of the wrapped steel pipe and ductile case iron pipe under Korean artificial earthquake has been shown as lower than that under actual overseas earthquake in the range from 0.1 to 0.4. The suggested seismic fragility curve by using Korean artificial earthquake can be exploited in a reasonable seismic design reflecting Korean local ground condition.

본 연구에서는 상수도시설물에 대해 손상단계를 기능수행과 붕괴방지로 나누고, 해외실측지진과 한반도형 인공지진에 대해 각각의 최대지반가속도에 따른 취약도 함수를 도출하였다. 손상단계 및 지반가속도를 이용하여 상수도시설물의 지진파에 따른 취약도 곡선을 도출하여 비교분석하였다. 해석결과, 도복장강관과 덕타일 주철관에 한반도형인공지진을 재하하는 경우, 해외실측지진을 재하하는 경우에 비하여 중앙값이 최소 0.1에서 최대 0.4까지 작아지는 것으로 나타났다. 본 연구에서 제안된 한반도형 인공지진을 이용한 지진취약도 곡선은 국내실정에 맞는 합리적인 내진 설계에 활용될 수 있을 것이다.

Keywords

References

  1. American Lifelines Alliance (2001), Guideline for the design of buried steel pipe, ASCE.
  2. Hwang H, and Huo J-R. (1994), Generation of hazard-consistent fragility curves for Seismic loss Estimation studies, Technical Report NCEER-97-0015.
  3. Kennedy, R.P. and Ravindra, M.k. (1984), Seismic Fragilities for Nuclear Power Plant Risk Studies, Nuclear Engineering and Design, 79(1), 47-68. https://doi.org/10.1016/0029-5493(84)90188-2
  4. Kim, S. H. and Shinozuka, M. (2004), Development of Bridges Retrofitted by Column Jacketing, Probabilistic Engineering Mechanics, 19(1), 105-112. https://doi.org/10.1016/j.probengmech.2003.11.009
  5. Kim, D. K. (2005), Dynamics of structure, Goomibook, Seoul, 579.
  6. Kwak, D. Y., Jeong, C. G., Lee, H. W., and Park, D. H., (2009), Development of New Probabilistic Seismic Hazard Analysis and Seismic Coefficients of Korea Part II: Derivation of Probabilistic Site Coefficients, Korean Geo-Environmental Society, 10(7), 111-115
  7. Lee, D. H., Jeon, J. M, Oh, J. G., and Lee,D. H. (2010), Earthquake Fragility Analysis of a Buried Gas Pipeline, Journal of the Earthquake Engineering Society of Korea, 14(5), 65-76. https://doi.org/10.5000/EESK.2010.14.5.065
  8. Mashaly, A., Datta, T. K. (1989), Seismic risk analysis of buried Pipelines, Journal of Transportation Engineering, ASCE, 115(3), 232-252. https://doi.org/10.1061/(ASCE)0733-947X(1989)115:3(232)
  9. Ministry of Environment (2007), Water corporation Standard Specification, Seoul.(in Korean)
  10. Ministry of Environment (2010), Waterworks Standards, Korea Water and Wastewater Works Association, Seoul.
  11. Park, D. H., Kwak, D. Y., Jeong, C. G. (2009), Development of New Probabilistic Seismic Hazard Analysis and Seismic Coefficients of Korea Part I: Application and Verification of a Novel Probabilistic Seismic Hazard Analysis Procedure, Korean Geo-Environmental Society, 10(7), 103-109
  12. Shinozuka, M., Takada, S., and Ishikawa, H. (1979), Some aspects of seismic risk analysis of underground lifeline systems, Journal of Pressure Vessel Technology, ASME, 101, 31-43. https://doi.org/10.1115/1.3454596
  13. Shinzuka, M., Feng M.Q., Lee, J.H., Naganuma, T. (2000), Statistical analysis of fragilit curve, Jurnal of Engineering Mechanics, ASCS, 126(12), 1224-1231. https://doi.org/10.1061/(ASCE)0733-9399(2000)126:12(1224)
  14. Seoul (2006), Soil Survey Manual, Seoul.
  15. Song, J. G. (2007), Development of Seismic Fragility Functions for Bridge Structures in Korea, National Disaster Management Institute, Seoul.

Cited by

  1. A Study on Freezing Assessment of the Water in the Z-Trap of Sewage Bay vol.12, pp.1, 2016, https://doi.org/10.15683/kosdi.2016.3.31.98