A Case Study on Energy Performance Measurement and Verification of an Energy Saving Office Building

에너지 절감형 업무용 건물의 에너지 성능 측정 및 검증에 관한 사례 연구

  • Received : 2014.12.04
  • Accepted : 2015.01.16
  • Published : 2015.02.28

Abstract

This study was to verify energy performance which was satisfying energy reduction target in design stage. Objective of building was called 'POSCO Green building' and was located in Yonsei International Campus, Songdo, Incheon, South Korea. Many green technologies were applied to Office Spaces which had been designed 60%, 80% energy reduction rate. 80% energy reduction zone was 50% saved more than 60% energy reduction zone in daily energy consumption comparison. Also, 80% energy reduction zone was 33% saved more than 60% energy reduction zone in weekly energy consumption comparison. Predicting energy consumption in winter season using for Regression Model, 80% energy reduction zone was saved 30% more than 60% energy reduction zone. However Energy consumption in field measurement was little more than energy reduction target in design stage.

Keywords

Acknowledgement

Supported by : 국토해양부

References

  1. CCGT(Chicago Center for Green Technology) 건물 사례에서의 실측과 검증을 통한 에너지 소비량 및 친환경 건물 관리에 관한 연구
  2. 국토교통부, 산업통상자원부, 건축물 에너지효율등급 인증 기준, 2013
  3. R. Vollaro, C. Guattari, Building energy performance analysis: A case study
  4. A. Pedrini, F.S. Westphal, R. Lamberts, A mehotodogy for building energy modeling and calibration in warm climates, builidng and environments 37, 2002, p.p. 903-912
  5. Case Study : Capuano Early Childhood Center, Massachusetts Technology Collaborative
  6. I. Iqbal, M.S. Al-Homoud, Parameric Analysis of alternative energy conservation measures in an office in hot and humid climate, building and environments 42, 2007, p.p.2166-2177 https://doi.org/10.1016/j.buildenv.2006.04.011
  7. M. Deru, P. Torcellini, M. Sheffer, A. Lau, Analysis for the design and energy performance of the Pennsylvania Department of Environmental Protection Cambria Office Building, National Renewable Energy Laboratory, NREL/TP-550-34931, March 2005