The main purpose of this study is to evaluate thermal management performance of data center with cold-aisle containment by using computational fluid dynamics (CFD) analysis. The main challenge of containment modeling in CFD is to consider the air leakage across the containment, which was neglected or considered based on the researchers' subjective assumption or complex measurement process. To properly evaluate the thermal management performance of containment, this study utilizes the building airtightness measurement data from building airflow simulation program (CONTAM) to model air leakage across containment. Based on the modeling strategy, the CFD simulation is conducted on modular data center test bed, and an experiment is also implemented in identical condition of CFD simulation. As a result, pressure distribution in the data center is properly modeled with the air leakage model, and the temperature measurement data are in good agreement with CFD results. Unlike intuition, the thermal management performance of containment is not excellent since there is some hot air recirculation through gaps between racks and the floor. This study also suggests that this recirculation can be alleviated by sealing the gaps between racks and the floor through CFD simulation.

Keywords

Acknowledgement

Supported by : 한국산업기술평가관리원

References

  1. 함상우, 김민휘, 윤동섭, 정재원, 컨테인먼트가 적용된 모듈러 데이터센터의 공조 팬 제어 방안에 관한 실험적 연구, 대한건축학회 춘계학술발표대회논문집 34(2), p.p. 285-287, 2014
  2. Abdelmaksoud, W.A., Dang, T.Q., Khalifa, H.E., and Schmidt, R.G., Improved Computational Fluid Dynamics Model for Open-Aisle Air-Cooled Data Center Simulations, Journal of Electronic Packaging, 135(3), pp. 030901, 2013 https://doi.org/10.1115/1.4024766
  3. Alkharabsheh, S.A., Shrivastava, S.K., and Sammakia, B.G., Effect of Cold Aisle Containment Leakage on Flow Rates and Temperatures in a Data Center, ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems, InterPACK 2013, 2, 2013
  4. ANSYS, ANSYS Fluent 15.0, 2013
  5. ASHRAE, Best Practices for Datacom Facility Energy Efficiency, 2nd edition, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Atlanta. GA, 2009a
  6. ASHRAE, 2009 ASHRAE Handbook: Fundamentals, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Atlanta. GA, 2009b
  7. ASHRAE, Thermal Guidelines for Data Processing Environments, 3rd edition, American Society of Heating, Re frigerating and Air-Conditioning Engineers, Inc. Atlanta. GA, 2012
  8. Arghode, V.K., Sundaralingam, V., Joshi, Y., and Phelps, W., Thermal Characteristics of Open and Contained Data Center Cold Aisle, Journal of Electronic Packaging, 136(1), pp. 011011, 2014 https://doi.org/10.1115/1.4026540
  9. Arghode, V.K., and Joshi, Y., Room Level Modeling of Air Flow in a Contained Data Center Aisle, Journal of Heat Transfer, 135(6), pp. 061901, 2013 https://doi.org/10.1115/1.4023597
  10. Bash, C.E., Patel, C.D., and Sharma, R.K., Efficient Thermal Management of Data Centers-Immediate and Long-Term Research Needs, HVAC&R Research, 9(2), p.p. 137-152, 2003 https://doi.org/10.1080/10789669.2003.10391061
  11. Chen, C., Zhao, Bin., Zhou, Wanting., Jiang, X., and Tan, Z., A methodology for predicting particle penetration factor through cracks of windows and doors for actual engineering application, Building and Environment, 47, p.p. 339-348, 2012 https://doi.org/10.1016/j.buildenv.2011.07.004
  12. Gondipalli, S., Bhopte, S., Sammakia, B., Madhusudan, I.K., and Rodger, S., Effect of Isolating Cold Aisles on Rack Inlet Temperature, 2008 11th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, I-THERM, art. no. 4544403, p.p. 1247-1254, 2008
  13. Herrlin, M.K., Airflow and Cooling Performance of Data Centers: Two Performance Metrics, ASHRAE Transactions 114(2), p.p. 182-187, 2008
  14. Joshi, Y., and Kumar P., Energy Efficient Thermal Management of Data Centers, Springer, 2012
  15. Khankari, K., Analysis of Air Leakage from Hot Aisle Containment Systems and Cooling Efficiency of Data Centers, ASHRAE Transactions 120(1), p.p. 1-8, 2014
  16. Koomey, J., Grwoth in data center electricity use 2005 to 2010, Analytics Press, Oakland, CA., 2011
  17. NIST, CONTAM Libraries, Appendix C2: Miscellaneous Residential Leakage Data, http://www.bfrl.nist.gov/IAQ analysis/CONTAM/table03_res.htm, 2011
  18. Patankar, S.V., Airflow and Cooling in a Data Center, Journal of Heat Transfer, 132(7), pp. 073001, 2010 https://doi.org/10.1115/1.4000703
  19. Patterson, M.K., Weidmann, R., Leberecht, M., Mair, M., and Libby, R.M., An Investigation into Cooling Sstem Control Strategies for Data Center Airflow Containment Architectures, ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, InterPACK 2011, p.p. 479-488, 2011
  20. Patterson, M.K., Martin, R., Oehsen, J.B., Pepin, J., Joshi, Y., Arghode, V.K., Steinbrecher, R., and King, J., A Field Investigation into the Limits of High-Density Air-Cooling, ASME 2013 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems, InterPACK 2013, 2, 2013
  21. Yoshii, A., Udagawa, Y., Yanagi, M., Matsuo, K., Maruyama, M., and Tominaga, T., Verification of Improved Air Conditioning Operation Measures in Server Rooms, Telecommunications Energy Conference (INTELEC), 2012 IEEE 34th International, p.p.1-5, 2012
  22. Zhai, J.Z., Hermansen, K.A., and Al-Saadi, S., The Development of Simplified Rack Boundary Conditions for Numerical Data Center Models, ASHRAE Transactions 118(2), p.p. 436-447, 2012