DOI QR코드

DOI QR Code

공장소음으로 인한 화재 경보음 인지 영향정도에 관한 연구

A study on Noise Generation and Awareness of the Fire Alarm Sound in the Factory

  • 이영삼 (세영 E&D 안전컨설팅 기술사사무소)
  • 투고 : 2015.10.20
  • 심사 : 2015.12.04
  • 발행 : 2015.12.31

초록

The people who are in the noise factory are difficult to hear and recognize about fire and to evacuate quickly when a fire occurs. This study was conducted to analyze workplace's background noise of 31 factories in Incheon and to know the workplace noise level comparing to fire alarm sound level. The measured average noise level was 96.8dB(A). Noise level of measured result was exceeded as 6.8dB(A) comparing to NFSC (National Fire Safety Code) noise level of 90dB. NFPA suggests that when background noise exceeds 85dB or more than that, other methods should be considered to know alarm sound. Also fire alarm sound should exceed more than 15dB(A) comparing to background noise level. Therefore it was concluded that the design of the fire alarm systems should not be applied to the workplace without considering background noise and it needs to be improved with regulations and the systems.

키워드

참고문헌

  1. National Fire Protection Association(NFPA)(2010), National Fire Alarm Code(NFPA 72).
  2. Min-Joo Lee, Hyoung-Bo Shim, In-Sung Hwang, Myung-Jun Kim(2008), "Experimental Study on the Sound Attenuation by the Characteristics of Fire Alarm Signal in the Residential Space", Korean Institute of Architectural Sustainable Environment and Building Systems Journal Fall Conference, 2008(10): 225-231.
  3. Ministry Of Public Administration And Se-curity(2009), National Fire Safety Code (NFSC), 201.
  4. Eun-Sun Baek, Geon-Jong Baek, Hoon Shin, Gil-Soo Jang(2009), "An Experimental Study on the Acoustic Characteristics of Fire Alarm Sound due to Voltage Variation", Korean Institute of Architectural Sustainable Environment and Building Systems Journal, 3(1): 10-15.
  5. Korea Occupational Safety Health Act, Part of health measure(2013).
  6. Young-Sam Lee, Dong-Ho Rie(2013), "A Study on Awareness Rate of the Fire Alarm Sound in the Factory", Journal of KOSHAM, 13(2):163-173.