A Study on the selection and noise test of elelctronic sensor for Vacuum Circuit Breaker

진공차단기용 전자식 센서의 선정 및 노이즈 시험에 관한 연구

  • Lee, Ki Seon (Department of Electrical Engineering, Gachon Unversity Seongnam) ;
  • Park, Jung Cheul (Department of Electrical Engineering, Gachon Unversity Seongnam) ;
  • Chu, Soon Nam (Department of Electrical Engineering, Gachon Unversity Seongnam)
  • Received : 2014.07.01
  • Accepted : 2014.09.10
  • Published : 2014.10.31

Abstract

This study is about the selection and noise test of electronic sensor which is preceded by electric Operating Cell(EOC) development using electronic sensor technology to solve the structural weakness of Mechanism Operated Cell(MOC) in VCB, and has a final target in product development minimizing contact malfunction of the chattering or rebounce states caused by existing MOC. In this test results, when opening and closing VCB, rising velocity of surge voltage in opening time was measured 4.2 times faster than closing time and noise decibel value was measured respectively 120dB and 110dB. When supplying 60kV power frequency overvoltage, we found that sensor output graph in VCB opening and closing times operated stably without distortion. When supplying 150kV $1.2{\times}50{\mu}s$ impulse frequency voltage, we found that voltage graph of output contact in sensor opening and closing sides maintained a normal condition without distortion, and when supplying 2500A current, we found that tested result of electric field noise operated stably without distortion.

본 연구는 진공차단기 기계식 보조접점(MOC)의 구조적인 취약성을 해결하기 위해 전자식 센서 기술을 이용한 전자식 보조접점(EOC) 개발에 선행되어야할 센서의 선정 및 노이즈 시험에 관한 것으로, 기존 기계적 보조접점(MOC)에서 발생하는 반복적인 떨림 및 반동 현상에 의한 접점 오동작을 최소화하는 제품을 개발하는 것을 최종 목표로 하였다. 실험 결과, 차단기 투입 및 개방시 개방시의 써지전압 상승속도가 투입시 보다 4.2배 빠른 것으로 측정되었고, 소음크기는 각각 120dB, 110dB로 측정되었다. 상용주파과전압 60kV를 인가하였을 때 진공차단기 투입 및 개방시 센서에서 출력되는 파형은 일그러짐이 없이 정상적으로 동작됨을 알 수 있었다. 그리고 150kV $1.2{\times}50{\mu}s$의 충격파를 인가하였을 때 센서의 투입 및 개방측 출력접점의 전압파형이 일그러짐이 없이 정상상태를 유지하였으며, 2500A의 전류를 인가하였을 때 자계 잡음을 측정한 결과, 전압파형이 일그러짐이 없이 정상적으로 동작하였다.

Keywords

References

  1. J.H.Hwang, J.C.Lee, Y.J.Kim,"Effects of Electrode Configurations on the Characteristics of Axial magnetic Fields in Vacuum Interrupter", Transactions of the Korean Society of mechanical engineers P7-P8, 2008. https://doi.org/10.3795/KSME-A.2008.32.1.007
  2. H.Y. Cho,L.Yu,"Optimal Design of Vacuum Circuit Breaker with Permanent Magnetic Actuator", J.of Industrial Science Technology and Institute, Vol.20,No.2, pp.69-78, 2006.
  3. I.M.Kim, J.H.Kim, S.H.Lee,"Switching Surge Analysis of Vacuum Circuit Breaker at Power Plant distribution lines", International Conference on Electrical Engineering pp. 2179-2182, 2002.
  4. Flurscheim, Charles. H, Power circuit breaker theory and design, IEE Power Engineering Series1, Chapter8, pp.356-P389.
  5. D.C. Bacvaro et al., "Risk of winding Insulation Breakdown in Large AC Motors Caused by Steep Switching Surge; Part 1, Computed Switching Surges", IEEE Trans. EC, Vol. !, No. 1, pp. 130-137, March 1986.
  6. "Testing Turn-to-Turn Insulation on Form-Wound Stator Coils for Alternating Current Rotating Electric Machines", IEEE Standard 522-1992.
  7. J.G.Kim,"Surge Characteristics Analysis and Reduction Method of Vacuum Circuit Breaker", The Transactions of the Korean Institute of Electrical Engineers pp.190-191, 2013. https://doi.org/10.5370/KIEE.2013.62.2.190
  8. Munir, B.S. Kadir, S.A. ,"Application of Surge Arrester on Vacuum Circuit Breaker ", Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific pp.1-4, 2012.