DOI QR코드

DOI QR Code

저에너지 주택용 단일 지열 교환기의 3차원 수치 모델링에 관한 연구

3-Dimensional Numerical Modeling of a Single Ground Heat Exchanger for Low-Energy Houses

  • 김의종 (프랑스 국립 과학 연구소(CNRS))
  • 투고 : 2014.02.05
  • 심사 : 2014.03.18
  • 발행 : 2014.05.30

초록

This paper aims at developing a three-dimensional numerical model of a single ground heat exchanger that would be enough to handle the heating and cooling loads of low-energy houses. As a reduced model (Linear Aggregation Method) previously developed is not yet sufficiently efficient in computation, some simplification schemes are newly proposed for the coupling of sub-zone models that are obtained from domain sub-structuring, which was mandatory to use the reduction method. The proposed model is compared to a reference model and the well-known existing model DST. Results from the 3-D numerical model implemented in Dymola are in a good agreement with the reference models, within a range of $0.2^{\circ}C$ in difference, and the computation efficiency is much enhanced with the proposed simplifications.

키워드

참고문헌

  1. Chiasson A. and Yavuzturk C. Assessment of the viability of hybrid geothermal heat pump systems with solar therma l collectors. ASHRAE Transactions, vol. 109, no. 2, pages 487-500, 2003.
  2. Eslami-nejad P. and Bernier M. A Preliminary Assessment on the Use of Phase Change Materials around Geothermal Boreholes. ASHRAE Transactions, vol. 119, no. 2, pages 31 2-321
  3. He M., Rees S. and Shao L. Simulation of a domestic ground source heat pump system using a transient numerical borehole heat exchanger model. In Building Simulation 2009, pages 607--614, Glasgow, Scotland, July 2009.
  4. Ingersoll L.R. and Plass. H.J. Theory of the ground pipe heat sourcefor the heat pump. Heating, Piping and Air conditioning, vol. 20, pages 119-122, 1948.
  5. Kim E.J., Roux J.J., Bernier M.A., and Cauret O., Three -dimensional numerical modeling of vertical ground heat exchangers: Domain decomposition and state model reduction, HVAC&R Research, 17(6) (2011a) 912-927.
  6. Kim, E.J., J.J. Roux, G. Rusaouen, and F. Kuznik. 2010. Numerical modelling of geothermal vertical heat exchangers for the short time analysis using the state model size reduction technique. Applied Thermal Engineering 30(6-7):706-14. https://doi.org/10.1016/j.applthermaleng.2009.11.019
  7. Marshall S.A. An approximate method for reducing the order of a linear system, Control 10 (1966) 642-643.
  8. Micha G.P. Approximation des systemes complexes par des modeles de dimension reduite, These d'Etat, Centre d'Orsay, Universite de Paris-sud, 1979.
  9. Trillat-Berdal V, Souyri B. and Fraisse G. Experimental st udy of a ground-coupled heat pump combined with thermal solar collectors. Energy and Buildings, vol. 38, no. 12, pages 1477-1484, 2006. https://doi.org/10.1016/j.enbuild.2006.04.005
  10. Kim EJ., Development of numerical models of vertical ground heat exchangers and experimental verification: Domain Decomposition and State Model Reduction Approach, These de doctorat, INSA de Lyon, 2011b