DOI QR코드

DOI QR Code

Heat Transfer Performance Variation of Condenser due to Non-uniform Air Flow

불균일한 풍속분포에 따른 응축기의 열전달 성능 변화

  • Lee, Won-Jong (School of Mechanical Engineering, Pusan National University) ;
  • Jeong, Ji Hwan (School of Mechanical Engineering, Pusan National University)
  • Received : 2014.11.30
  • Accepted : 2014.03.05
  • Published : 2014.04.10

Abstract

Heat transfer performance variation of a condenser caused by non-uniform distribution of air flow was investigated using a numerical simulation method. A heat exchanger used for a outdoor unit of a commercial heat pump system and represented by a numerical model was selected. Non-uniform profile of air-velocity was constructed by measuring the air velocity at various locations of the outdoor unit. Simulation was conducted for various refrigerant circuits and air flow conditions. Simulation results show that the heat transfer capacity was reduced depending on the air-flow rate and the refrigerant circuit configuration. It is also shown that the capacity reduction rate is increased as the average air velocity decreases.

Keywords

References

  1. Mao, J. N., Chen, H. X., Jia, H., and Wang, Y. Z., 2013, Effect of air-side flow maldistribution on thermal-hydraulic performance of the multi-louvered fin and tube heat exchanger, International Journal of Thermal Sciences, Vol. 73, pp. 46-57. https://doi.org/10.1016/j.ijthermalsci.2013.06.001
  2. Nair, S., Verma, S., and Dhingra, S. C., 1998, Rotary heat exchanger performance with axial heat dispersion, International Journal of Heat and Mass Transfer, Vol. 41, pp. 2857-2864. https://doi.org/10.1016/S0017-9310(98)00004-0
  3. Lee, K. and Oh, S., 2004, Optimal shape of the multi-passage branching system in a single-phase parallelflow heat exchanger, International Journal of Refrigeration, Vol. 27, pp. 82-88. https://doi.org/10.1016/S0140-7007(03)00099-9
  4. Timoney, D. J. and Foley, P. J., 1994, Some effects of air flow maldistribution on performance of a compact evaporator with R134a, Heat Recovery Systems and CHP, Vol. 14, No. 5, pp. 517-523. https://doi.org/10.1016/0890-4332(94)90054-X
  5. Jianying, G., Tieyu, G., Xiuling, Y., and Dong, H., 2008, Effects of air flow maldistribution on refrigeration system dynamics of an air source heat pump chiller under frosting conditions, Energy Conversion and Management, Vol. 49, pp. 1645-1651. https://doi.org/10.1016/j.enconman.2007.11.004
  6. Aganda, A. A., Coney, J. E. R., and Sheppard, C. G. W., 2000, Airflow maldistribution and the performance of a packaged air conditioning unit evaporator, Applied Thermal Engineering, Vol. 20, pp. 515-528. https://doi.org/10.1016/S1359-4311(99)00038-1
  7. Chang, Y. J. and Wang, C. H., 1997, A generalized heat transfer correlation for louver fin geometry, Int. J. Heat Mass Transfer, Vol. 40, No. 3, pp. 533-544. https://doi.org/10.1016/0017-9310(96)00116-0

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380