DOI QR코드

DOI QR Code

공기 및 지열 이용 Dual-Source 히트펌프 시스템의 성능실험 및 경제성 분석

The Performance Test and the Feasibility Study for a Dual-Source Heat Pump System Using the Air and Ground Heat Source

  • 남유진 (청주대학교 건축공학과) ;
  • 채호병 (청주대학교 건축공학과)
  • Nam, Yujin (Department of Architectural Engineering, Cheongju University) ;
  • Chae, Ho-Byung (Department of Architectural Engineering, Cheongju University)
  • 투고 : 2014.02.04
  • 심사 : 2014.03.24
  • 발행 : 2014.05.10

초록

Recently, the use of renewable energy has been increased due to growing concern on the energy-saving at buildings and the reduction of $CO_2$ emission. In the field of architecture, to reduce the energy consumption of heating, cooling and hot water supply, heat pump systems with renewable energy has been developed and used in various applications. However, there have been many of researches on the large-scale commercial heat pump systems, but the research and the field application of a compact heat pump system is rare. Therefore, in order to develop the compact heat pump for the small-scale residential building, this study conducted the performance test and feasibility study for a hybrid heat pump using the heat source of air, solar and ground. In the results of experiments through a trial product, the average COP of cooling mode with ground heat source was 4.75, and it of heating mode was 4.03. Furthermore, the average COP of cooling mode with air heat source was 2.60, and it of heating mode was 2.92. Finally, payback period of the system was calculated as 9.2 years.

키워드

참고문헌

  1. Xu, G., Zjamg, X., and Deng, S., 2006, A simulation study on the operating performance of a solar-air source heat pump water heater, Applied Thermal Engineering, Vol. 26, pp. 1257-1265. https://doi.org/10.1016/j.applthermaleng.2005.10.033
  2. Ozgener, O. and Hepbasli, A., 2005, Experimental performance analysis of a solar assisted ground-source heat pump greenhouse heating system, Energy and Buildings, Vol. 37, pp. 101-110. https://doi.org/10.1016/j.enbuild.2004.06.003
  3. Baek, N. C., Jeong, S. U., Yoon, E. S., and Lee, K. H., 2012, The development and performance analysis compact type solar thermal/ground coupled heat pump hybrid system for heating, cooling and heat water, Journal of the Korean Solar Energy Society, Vol. 32, No. 5, pp. 59-67. https://doi.org/10.7836/kses.2012.32.5.059
  4. Nam, Y. J., 2012, Study on the optimum design of a heat pump system using solar and ground heat, Korean Journal of SAREK, Vol. 24, No. 6, pp. 509-514. https://doi.org/10.6110/KJACR.2012.24.6.509
  5. Jun, C. H., Lee, H. S., Kim, J. D., and Yoon, J. I., 2006, Performance characteristics of air-cooled heat pump system using hydrocarbon refrigerants according to variation of outdoor temperature, Korean Journal of SAREK, Vol. 18, No. 3, pp. 218-224.
  6. Kim, Y. T., 2005, A study on the development of the representing day heating load model for the estimation of energy consumption in an apartment house, Journal of Architectural Institute of Korea, Vol. 21, No. 11, pp. 287-294.
  7. Chae, H. B., Nam, Y. J., and Kim, D. K., 2013, Study on the experimental analysis for a hybrid heat pump using the renewable heat source, Proceedings of the SAREK Spring Conference, pp. 416-419.

피인용 문헌

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380
  2. Sensitivity Analysis of the Design Factor for Vertical Closed-loop Geothermal System using Numerical Analysis : Focused on Heating Operation vol.18, pp.5, 2018, https://doi.org/10.12813/kieae.2018.18.5.055