DOI QR코드

DOI QR Code

실증운전을 통한 배가스 열회수 히트펌프 시스템의 성능 분석

Analysis of Performance of Heat Pump System with Flue Gas Heat Recovery through Field Test

  • 이승호 (한양대학교 기계공학부) ;
  • 이길봉 (한국에너지기술연구원 효율소재연구본부) ;
  • 이영수 (한국에너지기술연구원 효율소재연구본부) ;
  • 박상일 (한국에너지기술연구원 효율소재연구본부) ;
  • 고창복 (한국에너지기술연구원 효율소재연구본부) ;
  • 백영진 (한국에너지기술연구원 효율소재연구본부) ;
  • 이관수 (한양대학교 기계공학부)
  • Lee, Seung-Ho (Division of Mechanical Engineering, Hanyang University) ;
  • Lee, Gil-Bong (Energy Efficiency and Material Research Division, Korea Institute of Energy Research) ;
  • Lee, Young-Soo (Energy Efficiency and Material Research Division, Korea Institute of Energy Research) ;
  • Park, Sang-Il (Energy Efficiency and Material Research Division, Korea Institute of Energy Research) ;
  • Ko, Chang-Bok (Energy Efficiency and Material Research Division, Korea Institute of Energy Research) ;
  • Baik, Young-Jin (Energy Efficiency and Material Research Division, Korea Institute of Energy Research) ;
  • Lee, Kwan-Soo (Division of Mechanical Engineering, Hanyang University)
  • 투고 : 2013.08.09
  • 심사 : 2013.10.24
  • 발행 : 2014.01.10

초록

A field test of a 70 kW heat pump system with flue gas heat recovery was performed by an experiment at the Korea Institute of Energy Research. The flue gas is exhausted from a 320 RT absorption chiller-heater in the heating season. Using this flue gas, source water of the heat pump is heated by a condensed-type heat exchanger in the chimney. The operating characteristics of the heat recovery heat pump system were analyzed. Based on the results of the experiments, operating maps were obtained, and an optimum operating range is suggested, in which the return and heat source water temperature are $51^{\circ}C$ and $31^{\circ}C$, respectively. Additionally, economic analysis of this system was conducted and about 50% energy cost savings can be expected in the heating season.

키워드

참고문헌

  1. Cho, H. W., 1998, Condensing gas boilers with condensation latent heat recovery : Energy efficiency is higher than normal boiler, Ondol heating system, Korea Boiler Engineering Association, Vol. 59, pp. 76-79.
  2. Technology Diffusion Division of Korea Institute of Energy Research, 2003, Energy-saving technology trends(2003. 6), Vol. 30, pp. 109-145.
  3. Lim, B. I., 2005, Understanding of the condensing gas boiler, The energy equipment magazine, Korea Energy Information Center, Vol. 2005-08, pp. 152-163.
  4. KOGAS : Customer Support, http://www.kogas.or.kr/ kogas_kr/html/customer/customer_10_content.jsp.
  5. Lee, Y. S., 2012, Heat pump system with condensed heat recovery of flue gas and heat pump supply status, The magazine of the Society of Air-conditioning and Refrigeration Engineering of Korea, Vol. 41, No. 9, pp. 56-62.
  6. Korea Energy Management Corporation, 2012, Handbook of Energy and Economic Statistics in Korea.
  7. Morten, B. B. and Henrik L., 2007, Large-Scale Heat Pumps in Sustainable Energy Systems : System and Project Perspectives, Thermal Science, Vol. 11, No. 3, pp. 143-152.
  8. Park, S. I., 2009, Technology of condensed heat recovery of boiler flue gas, The magazine of the Society of Air-conditioning and Refrigeration Engineering of Korea, Vol. 38, No. 2, pp. 36-40.
  9. Korea Electronic Power Corporation, 2012, KEPCO in Brief.
  10. Korea Gas Corporation, 2012, City gas heat system explanation document.

피인용 문헌

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380