DOI QR코드

DOI QR Code

저압용차단기 전원 개폐시 개인용 PC에 미치는 영향 분석

Analysis of Effect on Personnel Computer in case of turning off Power supply of Circuit Breaker for Low Voltage

  • 투고 : 2014.10.28
  • 심사 : 2014.11.12
  • 발행 : 2014.12.31

초록

This paper describes the analysis of the effect on personnel computer in case of turning off power supply of main breaker in general electrical installation. In order to analyze the effect on personnel computer in case of turning off the power supply of main breaker, the switching impulse generator has been designed and fabricated which makes it possible to evaluate the effect on electrical product by switching impulse. The switching impulse tests were carried out for personnel computer according to applied voltage and number of switching impulse. As a consequence, switching impulse had not a significant influence on personnel computer in this study. The varistor of power input section functions as a protection of switching impulse as well as lightning impulse. The results will be used to related organization, and electrical product manufacturer, and residents.

키워드

참고문헌

  1. Hyoung-Jun Gil et al., "Research on Analysis of Cause of Occurrence and Prevention Measures for Minor Accident", Korea Electrical Safety Corporation, pp.3-18, 2013.
  2. Hyoung-Jun Gil et al., "Investigation and Analysis for preventing Minor Accident in General Electrical Installation", Fall Conference of the Korean Society of Safety, pp.88, 2013.
  3. Korea Electrical Safety Corporation, "Processing Method of Check Work", Korea Electrical Safety Corporation, pp.4-7, 2012.
  4. Megger, "A Guide to Diagnostic Insulation Testing above 1kV", pp.14-30, 2012.
  5. Korean Agency for Technology and Standards, "KS C IEC 60060-1", pp.1-20, 2010.
  6. B.H. Lee, "High Voltage and Current Engineering", Cheongmungak, pp.4-30, 1993.
  7. C.S. Choi, D.W. Kim, Y.S. Kim, K.Y. Lee, "The Arc Dispersion Properties by Switching of High Sensitivity Type RCD Contacts", Korean Institute of Fire Science & Engineering, Vol.19, No.2, pp.1-6, 2005.
  8. Korean Agency for Technology and Standards, "IEC 60364-5-53", pp.1-12, 2005.
  9. B.H. Lee, "Protection of Information and Communication Facilities against Lightning", Publishing Department of INHA University, pp.110-168, 2003.
  10. Hyoung-Jun Gil et al., "Research on Assessment of Potential Interference between Individual Grounding Electrodes Using an Electrolytic Tank Modeling Method", The Korean Institute of Illuminating and Electrical Installation Engineers, Vol.22, No.3, pp.27-33, 2008. https://doi.org/10.5207/JIEIE.2008.22.3.027
  11. Hyoung-Jun Gil et al., "Field Application Condition and Improvement solution for Surge Protective Device Installed in Buildings", Fall Conference of The Korean Institute of Electrical Engineers, pp.179-181, 2010.