Virtual Inertial Control of a Wind Power Plant using the Maximum Rate of Change of Frequency

주파수의 최대 변화율을 이용한 풍력단지 가상관성제어

  • Kim, Dooyeon (Dept. of Electrical Engineering, Chonbuk National University) ;
  • Kim, Jinho (Dept. of Electrical Engineering, Chonbuk National University) ;
  • Lee, Jinshik (Dept. of Electrical Engineering, Chonbuk National University) ;
  • Kim, Yeon-Hee (Dept. of Electrical Engineering, Chonbuk National University) ;
  • Chun, Yeong-Han (Dept. of Electrical Engineering, Hongik University) ;
  • Kang, Yong Cheol (Dept. of Electrical Engineering, Chonbuk National University)
  • 김두연 (전북대 대학원 전기공학과) ;
  • 김진호 (전북대 대학원 전기공학과) ;
  • 이진식 (전북대 대학원 전기공학과) ;
  • 김연희 (전북대 대학원 전기공학과) ;
  • 전영환 (홍익대 전자전기공학부) ;
  • 강용철 (전북대 공대 전기공학과)
  • Received : 2013.05.20
  • Accepted : 2013.06.17
  • Published : 2013.07.01

Abstract

In a conventional power system, the frequency is recovered to the nominal value by the inertial, primary, and secondary responses of the synchronous generators (SGs) after a large disturbance such as a generator tripping. For a power system with high wind penetration, the system inertia is significantly reduced due to the maximum power point tracking control based operation of the variable speed wind generators (WGs). This paper proposes a virtual inertial control for a wind power plant (WPP) based on the maximum rate of change of frequency to release more kinetic energy stored in the WGs. The performance of the proposed algorithm is investigated in a model system, which consists of a doubly fed induction generator-based WPP and SGs using an EMTP-RV simulator. The results indicate that the proposed algorithm can improve the frequency nadir after a generator tripping. In addition, the algorithm can lead the instant of a frequency rebound and help frequency recovery after the frequency rebound.

Keywords

References

  1. Specification of power system reliability and power quality, Ministry of Knowledge Economy, December 2009.
  2. Operational standard of the ancillary service for a power system operation, Korea Power Exchange, Aug. 2010.
  3. Global Wind Energy Outlook 2012, GWEC, November 2012.
  4. The 6th basic plan of electricity supply and demand, Ministry of Knowledge Economy, Feb. 2013.
  5. J. B. Ekanayake, L. Holdsworth, and N. Jenkins, "Control of doubly fed induction generator wind turbine," IEE Power Eng., vol. 17, no. 1, pp. 28-32, Feb. 2003.
  6. J. B. Ekanayake and N. Jenkins, "Comparison of the Response of Doubly Fed and Fixed-Speed Induction Generator Wind Turbines to Changes in Network Frequency", IEEE Trans. on Energy conversion, vol. 19, No. 4, pp. 800-802, December 2004. https://doi.org/10.1109/TEC.2004.827712
  7. J. Morren, S. Haan, W. L. Kling, and J. A. Ferreira, "Wind turbines emulating inertia and supporting primary frequency control," IEEE Trans. on Power systems, vol. 21, no. 1, pp. 433-434. Feb. 2006. https://doi.org/10.1109/TPWRS.2005.861956
  8. G. Ramtharan, J. B. Ekanayake, and N. Jenkins, "Frequency support from doubly fed induction generator wind turbines," IET Renew. Power Gen., vol. 1, pp. 3-9, 2007. https://doi.org/10.1049/iet-rpg:20060019
  9. B. Shen, B. Mwinyiwiwa, Y. Zhang, and B. Ooi, "Sensorless Maximum Power Point Tracking of Wind by DFIG Using Rotor Position Phase Lock Loop," IEEE Trans. Power Elect. vol. 24, no. 4, pp. 942-951. 2009. https://doi.org/10.1109/TPEL.2008.2009938