The parameters of electromechanical modes offer considerable insight into the dynamic stability properties of a power system. This paper presents a results of a LFO(low-frequency oscillation) based on the time-synchronized signals measured by synchrophasor in the rolling blackout. Spectral analysis was performed, and critical parameters were estimated using the data acquired from synchrophasors installed in the KEPCO system. As significant modes, a 0.68 Hz oscillation mode that occurred prior to the forced load shedding in the rolling blackout was estimated. Such an oscillation mode can cause an uncontrollable blackout. Therefore, the system should be operated so that significant oscillation modes are not activated. This results can serve as a reference in the future for reliable system operation in the event of a similar blackout.

Keywords

References

  1. IEEE standard for synchrophasors for power systems, IEEE Std C37. 118-2005, 2005.
  2. I. Kamwa, R. Grondin, "PMU configuration for system dynamic performance measurement in large multiarea power systems," IEEE Trans. on Power Systems, Vol. 17, No. 2, pp.385-394, 2002. https://doi.org/10.1109/TPWRS.2002.1007908
  3. J. De La Ree, V. Centeno, J. S. Thorp, A. G. Phadke, "Synchronized phasor measurement applications in power systems," IEEE Trans. on Smart Grid, vol. 1, no. 1, pp.250-257, June 2010.
  4. F. Hauer, "Validation of phasor calculations in the macrodyne PMU for California-Oregon transmission project tests of March 1993," IEEE Trans. Power Delivery, vol 11, no 3, pp.1224-1231, July 1996. https://doi.org/10.1109/61.517475
  5. A. G. Phadke, R. M. de Moraes, "The wide world of wide-area measurement," IEEE Power Energy, Vol. 6, No. 5, pp.52-65, Oct. 2008.
  6. D. Atanackovic, J. H. Clapauch, G. Dwernychuk, J. Gurney, H. Lee, "First steps to wide area control," IEEE Power Energy, Vol. 6, pp.61-68, 2008.
  7. J. F. Hauer, W. A. Mittelstadt, K. E. Martin, J. W. Burns, H. Lee, J. W. Pierre, D. J. Trudnowski, "Use of the WECC WAMS in wide-area probing tests for validation of system performance and modeling WECC disturbance monitoring work group," IEEE Trans. Power Systems, Vol. 24, No. 1, pp.250-257, Feb. 2009. https://doi.org/10.1109/TPWRS.2008.2009429
  8. K. S. Shim, "Detection of low frequency oscillation in KEPCO system and WAMAC technology," KIEE 2011 Summer Meeting, July 2011.
  9. S. T. Kim, "Technology of Smart WAMAC infra construction," KIEE 2011 Summer Meeting, July 2011.
  10. K. S. Shim, S. T. Kim, H. K. Nam, J. H. Choi, B. H. Yoon, "Analysis of low frequency oscillation based on K-WAMS in 9.15 rolling blackout," KIEE 2012 Summer Meeting, pp.15-17, July 2012.
  11. M. Klein, G. J. Rogers, P. Kundur, "A fundamental study of inter-area oscillations in power systems," IEEE Trans. on Power Systems, Vol. 6, No. 3, pp.914-921, Aug. 1991. https://doi.org/10.1109/59.119229
  12. EPRI, PhaseII: frequency domain analysis of low frequency analysis oscillations in large power system, Vol.2, Final Report EPRI EL-2348, 1982.
  13. KW-PSS. Available at:http://www.kepri.re.k/kwpss /kor/ index.jsp.
  14. SSAT. Available at:http://www.dsatools.com/html/prod_ ssat.php.
  15. J. F. Hauer, C. J. Demeure, and L. L. Scharf, "Initial results in Prony analysis of power system response signals," IEEE Trans. Power Systems, Vol. 5, No. 1, pp. 80-89, Feb. 1990. https://doi.org/10.1109/59.49090
  16. J. W. Pierre, D. J. Trudnowski, M. K. Donnelly, "Initial results in electromechanical mode identification from ambient data," IEEE Trans. Power Systems, Vol. 12, No. 3, pp.1245-1251. Aug. 1997. https://doi.org/10.1109/59.630467
  17. B. Mohammadi-Ivatloo, M. Shiroei, M. Parniani, "Online small signal stability analysis of multi-machine systems based on synchronized phasor measurements," Electric Power Systems Research, Vol. 81, No. 10, pp.1887-1896. Oct 2011. https://doi.org/10.1016/j.epsr.2011.05.014
  18. L. Ljung, System identification, theory for the user, Prentice Hall Inc., New Jersey, 1999.
  19. K. S. Shim, H. K. Nam, "A fast parameter estimation of time series data using discrete Fourier transform," Trans. of KIEE, Vol.55, No.7, pp.265-272, July 2006.
  20. P. Stoica, R. Moses, Spectral analysis of signals, Prentice Hall Inc., New Jersey, 2004.
  21. P. A. Lynn, W. Fuerst, Introductory digital signal processing, John Wiley & Sons, Inc., New York, 1998.
  22. Ministry of Economy, Trade and Industry, "Situation of rolling blackout implementation," 2011.
  23. Mack Grady, "The ERCOT rolling blackout," Texas Synchro-Phasor Network Special Report, Feb. 2011.
  24. J. Machowski, J. W. Bialek, J. R. Bumby, "Power system dynamics: stability and control," John Wiley & Sons, Inc., UK, 2008.
  25. D. J. Trudnowski, J. W. Pierre, N. Zhou, J. F. Hauer, M. Parashar, "Performance of three mode-meter block-processing algorithms for automated dynamic stability assessment," IEEE Trans on Power Systems, Vol. 23, No. 2, pp.680-690, 2008. https://doi.org/10.1109/TPWRS.2008.919415