DOI QR코드

DOI QR Code

An improvement to seismic design of substation support structures

  • Mohammadi, Reza Karami (Civil Engineering Department, K. N. Toosi University of Technology (KNTU)) ;
  • Akrami, Vahid (Civil Engineering Department, Amirkabir University of Technology) ;
  • Nikfar, Farzad (Civil Engineering Department, McMaster University)
  • Received : 2011.08.18
  • Accepted : 2013.02.23
  • Published : 2013.03.25

Abstract

The acceleration that the electrical equipment experiences on a structure can be several times the ground acceleration. Currently, substation support structures are being designed according to ASCE (Substation Structure Design Guide 2008), without any consideration about effects of these structures on dynamic behavior of mounted equipment. In this paper, a parametric study is implemented in order to improve seismic design of candlestick substation structures based on this design guide. To do this, dynamic amplification factor (DAF) of different candlestick support-equipment combinations is evaluated and compared to the target DAF presented in IEEE STD 693 (2006). Based on this procedure, a new criterion is developed to restrict maximum acceleration at support-equipment intersection.

Keywords

References

  1. Architectural Institute of Japan (AIJ) (1998), Investigation Report on the Great Hanshin-Awaji Earthquake, Volume 3: Urban Disaster Prevention System, Marusen Corp. Press, Tokyo, Japan.
  2. ASCE Guide (1996), Guide to Improved Earthquake Performance of Electric Power Systems, ASCE Manuals and Reports on Engineering Practice No. 96.
  3. ASCE Manual (2008), Substation Structures Design Guide, ASCE Manuals and Reports on Engineering Practice No. 113.
  4. ASCE-TCLEE (1997), Northridge Earthquake: Lifeline performance and post earthquake response, American Society of Civil Engineering Technical Council on Life Line Earthquake Engineering.
  5. Clough, R.W. and Penzien, J. (1993), Dynamics of Structures, 3nd Ed., McGraw-Hill Publishing Company, New York.
  6. Chang, L. and Wu, Z. (2011), "Performance and reliability of electrical power grids under cascading failures", Int. J. Elec. Power Energy Syst., 33(8), 1410-1419. https://doi.org/10.1016/j.ijepes.2011.06.021
  7. Chopra, A.K. (2007), Dynamics of Structures; Theory and Application to Earthquake Engineering, 3rd Edition, Prentice Hall.
  8. Dastous, J.B., Filiatrault, A. and Pierre, J.R. (2004), "Estimation of displacement at interconnected points of substation equipment subjected to earthquake", IEEE Trans. Power Del., 19(2), 618-628. https://doi.org/10.1109/TPWRD.2003.823203
  9. Dastous, J.B. (2007), "Guidelines for seismic design of flexible buswork between substation equipment", Earthq. Eng. Struct. Dyn., 36, 191-208. https://doi.org/10.1002/eqe.619
  10. Dastous, J.B. and Pierre, J.R. (2007), "Design methodology for flexible buswork between substation equipment subjected to earthquake", IEEE Trans. Power Del., 22(3), 1490-1497. https://doi.org/10.1109/TPWRD.2007.899803
  11. Feizi, B., Saadeghvaziri, M.A., Ersoy, S. and Ashrafi, A. (2008), Seismic Evaluation and Rehabilitation of Critical Electric Power System Components, Department of Civil and Environmental Engineering, New Jersey Institute of Technology, Newark, NJ 07102.
  12. FEMA 440 (2005), Improvement of Nonlinear Static Seismic Analysis Procedures, Federal Emergency Management Agency (FEMA), Washington, D.C..
  13. Gilani, A.S., Whittaker, A.S., Fenves, G.L. and Chen, C. (2000), Seismic Evaluation and Analysis of 230-kV Disconnect Switches, PEER Report 2000/06, University of California, Berkeley.
  14. Hatami, M., Ghafory-ashtiani, M. and Hosseini, M. (2004), "Experimental and analytical study of a high voltage instrument transformer", 13th World Conference on Earthquake Engineering, Vancouver, B.C., Canada.
  15. IEEE Standard 693 (2006), IEEE Recommended Practice for Seismic Design of Substations, IEEE, 3 Park Avenue, New York, NY 10016-5997, USA.
  16. Matt, H. and Filiatrault, A. (2004), Seismic Qualification Requirements for Transformer Bushings, Department of Structural Engineering University of California, San Diego La Jolla, California 92093-0085.
  17. Pham, T. (2005), Two-Dimensional Shaking Table Test of Transformer Bushing with Seismic Isolation Device, MCEER Report, Department of civil and environmental Engineering, University of California at Irvin.
  18. Shinozuka, M., Dong, X., Chen, T.C. and Jin, X. (2007), "Seismic performance of electric transmission network under component failures", Earthq. Eng. Str. Dyn., 36(2), 227-244. https://doi.org/10.1002/eqe.627
  19. Takhirov, S.M., Fenves, G.L. and Fujisaki, E. (2005), Seismic Qualification and Fragility Testing of Line Break 550 kV Disconnect Switches, PEER Report, University of California, Berkeley.
  20. Wen, B. and Niu, D. (2011), "Seismic response analysis of substation involving interaction of main structure-electrical equipment", Adv. Mat. Res., 163-167, 4022-4026.

Cited by

  1. Considering seismic interaction effects in designing steel supporting structure for surge arrester vol.132, 2017, https://doi.org/10.1016/j.jcsr.2017.01.012
  2. Effects of sheds and cemented joints on seismic modelling of cylindrical porcelain electrical equipment in substations vol.12, pp.1, 2013, https://doi.org/10.12989/eas.2017.12.1.055