DOI QR코드

DOI QR Code

Heat Transfer Characteristics of Spray Cooling up to Critical Heat Flux on a Low-fin Enhanced Surface

Low-fin 촉진 표면에서 임계 열유속까지의 분무 냉각 열전달 특성

  • Received : 2013.06.10
  • Published : 2013.09.10

Abstract

Spray cooling is a technology of increasing interest for electronic cooling and other high heat flux applications. In this study, heat transfer coefficients (HTCs) and critical heat fluxes (CHFs) were measured on a smooth square flat copper heater of $9.53{\times}9.53$ mm at $36^{\circ}C$ in a pool, with a smooth flat surface, and 26 fpi. Low-fin surfaces were used to see the change in HTCs and CHFs according to the surface characteristics, and FC-72 was used as the working fluid. FC-72 fluid had a significant influence on the heat transfer characteristics of the spray over the cooling surface. HTCs were taken from 10 $kW/m^2$ to critical heat flux, for all surfaces. Test results with Low-fin showed that the CHFs of all the enhanced surface were greatly improved. It can be said that the surface form affects the heat transfer coefficient and critical heat flux.

Keywords

References

  1. Moon, S. H., Hwang, G., Kang, S. Y., and Cho, K. I., 2010, Development of Small Flat Plate Type Cooling Device, Korean J. of Air-Conditioning and Refrigeration Engineering, Vol. 22, No. 9, pp. 614-619.
  2. Bhowmik, H., Tso, C. P., Tou, K. W., and Tan, F. L., 2005, Convection heat transfer from discrete heat sources in a liquid cooled rectangular channel, J. of Applied Thermal Engineering, Vol. 25, No. 16, pp. 2532-2542. https://doi.org/10.1016/j.applthermaleng.2004.11.022
  3. Agwu Nnanna, A. G., 2006, Application of refrigeration system in electronics cooling, J. of Applied Thermal Engineering, Vol. 26, No. 1, pp. 18-27. https://doi.org/10.1016/j.applthermaleng.2005.04.012
  4. Kim, Y. H., Kim, C., Lee, K. J. and Kim, Y. C., 2006, An Experimental Study on Boiling Heat Transfer of PF5060 on the Shape and Orientation of Micro-fin Surfaces, Trans. Korean Soc. Mech. Eng. B, Vol. 30, No. 1, pp. 74-81. https://doi.org/10.3795/KSME-B.2006.30.1.074
  5. Kim, T. G., Kim, Y. H., and Lee, K. J., 2006, Characteristics of Cooling for the Adjacent Double Micro-Porous Coated Surfaces in PF5060, Trans. Korean Soc. Mech. Eng. B, Vol. 30, No. 7, pp. 646-655. https://doi.org/10.3795/KSME-B.2006.30.7.646
  6. Park, K. J. and Jung, D., 2008, Pool boiling heat transfer coefficients up to critical heat flux, Korea Journal Air-Conditioning and Refrigeration Engineering, Vol. 20, No. 9, pp. 571-580.
  7. Lee, Y. and Jung, D., 2011, Pool boiling heat transfer coefficients up to critical heat flux on low-fin and turbo-B surfaces, Korea Journal Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 3, pp. 179-187. https://doi.org/10.6110/KJACR.2011.23.3.179
  8. Hsu, Y. Y. and Graham, R. W., 1976, Transport Processes in Boiling and Two-Phase System, Hemisphere Publishing Company, Washington, D. C.
  9. Van Stralen, S. J. D., 1968, The Growth Rate of Vapor Bubbles in Superheated Pure Liquid and Binary Mixtures, International Journal of Heat Mass Transfer, Vol. 11, pp. 1467-1512. https://doi.org/10.1016/0017-9310(68)90112-9
  10. Mudawar, I. and Valentine, W. S., 1989, Determination of the local quench curve for spray-cooled metallic surfaces, Journal of Heat Treating, Vol. 7, No. 2, pp. 107-121. https://doi.org/10.1007/BF02833195
  11. Grissom, W. M. and Wierum, F. A., 1981, Liquid spray cooling of a heated surface, International Journal of Heat and Mass Transfer, Vol. 24, No. 2, pp. 261-271. https://doi.org/10.1016/0017-9310(81)90034-X
  12. Fujimoto, H., Hatta, N. Asakawa, H., and Hashimoto, T., 1997, Predictable modeling of heat transfer coefficient between spraying water and a hot surface above the Leidenfrost temperature, ISIJ International, Vol. 37, No. 5, pp. 492-497. https://doi.org/10.2355/isijinternational.37.492
  13. Estes, K. A. and Mudawar, I., 1995, Correlation of Sauter Mean Diameter and Critical Heat Flux for Spray Cooling of Small Surfaces, International Journal of Heat and Mass Transfer, Vol. 38, pp. 2985-2996. https://doi.org/10.1016/0017-9310(95)00046-C
  14. Mudawar, I. and Estes, K. A., 1996, Optimizing and Predicting CHF in Spray Cooling of a Square Surface, ASME J. of Heat Transfer, Vol. 118, pp. 672-679. https://doi.org/10.1115/1.2822685
  15. Visaria, M. and Mudawar, I., 2008, Theoretical and Experimental Study of Effects of Spray Inclination on Two-Phase Spray Cooling and Critical Heat Flux, International Journal of Heat and Mass Transfer, Vol. 51, pp. 2398-2410. https://doi.org/10.1016/j.ijheatmasstransfer.2007.08.010
  16. Lin, L. and Ponnappan, R., 2003, Heat transfer characteristics of spray cooling in a closed loop, Int. J. of Heat and Mass transfer, Vol. 46, pp. 3737-3746. https://doi.org/10.1016/S0017-9310(03)00217-5
  17. Silk, E. C., Kim, J., and Kiger, K., 2006, Spray Cooling of Enhanced Surfaces (Impact of Structured Surface Geometry and Spray Axis Inclination), International Journal of Heat and Mass Transfer, Vol. 49, pp. 4910-4920. https://doi.org/10.1016/j.ijheatmasstransfer.2006.05.031
  18. Hsieh, C. C. and Yao, S. C., 2006, Evaporative Heat Transfer Characteristics of a Water Spray on Micro- Structured Silicon Surfaces, International Journal of Heat and Mass Transfer, Vol. 49, pp. 962-974. https://doi.org/10.1016/j.ijheatmasstransfer.2005.09.013
  19. Kline, S. J. and McClintock, F. A., 1953, Describing uncertainties in single-sample experiments, Mechanical Engineer, Vol. 75, pp. 3-8.
  20. Gorenflo, D. and Fath, W., 1987, Pool boiling heat transfer on the outside of finned tubes at high saturation pressures, Proc. 17th Int. Congr, Refrig., pp. 955-960.

Cited by

  1. Heat Transfer Characteristics of Spray Cooling Up to Critical Heat Flux on Thermoexcel-E Enhanced Surface vol.28, pp.9, 2016, https://doi.org/10.6110/KJACR.2016.28.9.373