DGA Interpretation of Oil Filled Transformer Condition Diagnosis

  • Alghamdi, Ali Saeed (Institute of High Voltage and High Current, Faculty of Electrical Engineering, Universiti Teknologi/Technical and Vocational Training Corporation, Jeddah Secondary and Vocational Institute) ;
  • Muhamad, Nor Asiah (Institute of High Voltage and High Current, Faculty of Electrical Engineering, Universiti Teknologi) ;
  • Suleiman, Abubakar A. (Institute of High Voltage and High Current, Faculty of Electrical Engineering, Universiti Teknologi/National Agency for Science and Engineering Infrastructure)
  • Received : 2012.06.12
  • Accepted : 2012.09.18
  • Published : 2012.10.25

Abstract

DGA is one of the most recent techniques developed to diagnose the fault condition on oil filled insulation transformers. There are more than 6 known different methods of DGA fault interpretation technique and so there is the likelihood that they may vary in their interpretations. A series of combined interpretation methods that can determine the power transformer condition faults in one assessment is therefore needed. This paper presents a computer program- based system developed to combine four DGA assessment techniques; Rogers Ratio Method, IEC Basic Ratio Method, Duval Triangle method and Key Gas Method. An easy to use Graphic User Interface was designed to give a visual display of the four techniques. The result shows that this assessment method can increase the accuracy of DGA methods by up to 20% and the no prediction result had been reduced down to 0%.

Keywords

References

  1. M.Wang, et al., "Review of Condition Assessment of Power Transformers in Service," IEEE Electrical Insulation Magazine, IEEE, 2002, 2002 [DOI: http://dx.doi.org/10.1109/MEI.2002.1161455].
  2. P. Gill, "Electrical Power Equipment Maintenance and Testing," 2nd Edition, CRC Press, 2009, 2009 [http://www.crcnetbase.com/isbn/9781420017557].
  3. ANSI/IEEE-Std-62-1995, "IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus-Part1:Oil Filled Power Transformers, Regulators, and Reactors" IEEE Power Engineering Society-1995, 1995 [DOI: http://dx.doi.org/10.1109/IEEESTD.1995.122640].
  4. R. Rogers, "IEEE and IEC codes to interpret incipient faults in transformers, using gas in oil analysis," Electrical Insulation, IEEE Transactions on, pp. 349-354, 1978 [DOI: http://dx.doi.org/10.1109/TEI.1978.298141].
  5. N. A. Muhamad, et al., "Comparative Study and Analysis of DGA Methods for Transformer Mineral Oil," IEEE Lausanne Power Tech pp. 45-50, 2007 [DOI: http://dx.doi.org/10.1109/PCT.2007.4538290].
  6. N. A. Muhamad, et al., "Dissolved gas analysis of faults in biodegradable oil transformer insulating systems," International Conference on Condition Monitoring and Diagnosis, pp. 663-666, 2008 [DOI: http://dx.doi.org/10.1109/CMD.2008.4580373].
  7. M. Duval and A. de-Pabla, "Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases," IEEE Dielectrics and Electrical Insulation Society Electrical Insulation Magazine vol. 17, 2001 [DOI: http://dx.doi.org/10.1109/57.917529]
  8. T. Snow and M. McLarnon, "The implementation of continuous online Dissolved Gas Analysis (DGA) monitoring for all transmission and distribution substations," International Symposium on Electrical Insulation (ISEI), pp. 1-4, 2010 [DOI: http://dx.doi.org/10.1109/ELINSL.2010.5549358]
  9. J. H. Sun and S. B. Han, "Development of Oil Immersed Transformer Management Technologies by Using Dissolved Gas Analysis," International Conference on Properties and applications of Dielectric Materials, pp. 683-686, 2006 [DOI: http:// dx.doi.org/10.1109/ICPADM.2006.284269]