Abstract
In order to dispose of the LILW(low and intermediate level radioactive waste) stored at KAERI, the radwaste drum assay system will be introduced to evaluate the radioisotopes inventory of stored drums. At present, the construction project of the dedicated assay facility to operate it and carry out routine maintenance of that equipment has been conducting at the radwaste treatment facility. Since that facility will be constructed in front of a 1st radwaste storage facility as well as the radwaste drums to be assayed and the transmission source in the radwaste drum assay system are in that facility, they could act as the radioactive sources and then, would affect the dose rate at the inside and the outside of the facility. Therefore, the radiation shielding should be evaluated through the concrete wall near to the radioactive sources whether the wall thickness is sufficient against the regulations. In this study, the radiation safety for the concrete wall around the radiation controlled area in the radwaste drum assay facility was evaluated by the MCNP code. From the evaluation results, the thickness of those concrete walls which are under consideration of about 30 cm was enough to shield the radiation from the radioactive sources.
한국원자력연구원 내 저장중인 중 저준위방사성폐기물의 안전한 영구처분을 위하여 방사성폐기물처리시설에서는 이들 저장폐기물의 핵종재고량 평가를 위한 드럼핵종분석장치의 도입을 기획하고 있으며, 이 장치를 운영하고 유지보수하기 위한 전용의 평가시설 구축을 추진하고 있다. 이 평가시설 외부에는 제1방사성폐기물저장시설이 인접하여 있으며 내부에는 평가대상드럼들과 드럼핵종분석장치의 밀도보정용 선원 등이 존재함으로 이들이 방사선원항으로 작용하여 평가시설 내 외부의 선량률에 영향을 미치게 된다. 따라서 방사선원항 주변의 콘크리트 구조물에 대한 방사선차폐 영향을 평가하여야 한다. 본 연구에서는 MCNP 코드를 이용하여 해당 방사선원항으로부터 평가시설 내부 방사선관리구역을 둘러싸고 있는 콘크리트 구조물에 대한 방사선 안전성을 평가하였다. 평가결과 현재 고려되고 있는 콘크리트 구조물의 약 30 cm 두께는 해당 방사선원항으로부터의 방사선을 차폐하기에 충분한 것으로 확인되었다.