Abstract
As the result of reviewing the linked treatment of water quality for treating process at public livestock wastewater treatment facilities for fair selection of the proper linked process in case of linking sewage treatment plant for livestock wastewater, in case of wastewater processed by bio-reactor that is only biologically-treated, the load factor showed relatively high as 1.67%(base on design quality), 2.59%(base on operation quality) regarding COD and 3.69%(base on design quality), 7.67%(base on operation quality) regarding $COD_{Mn}$ but it is judged that there is nearly no influence on the operation of sewage treatment plan. And, in case of oxidized flotation-treated water & biofiltlation-treated water that are the advanced wastewater treatment, the load factor is approximately 1% and there is concern about the installation of excessive facilities in case of installing the advanced wastewater treatment. So, in case of considering the economic efficiency & stable operation of sewage treatment plant S, it is judged to be desirable to link with wastewater processed by bio-reactor that is biologically-treated.
처리공정별 연계처리수질을 검토한 결과 생물학적처리만 거친 생물반응조 처리수의 경우 연계부하율이 $COD_{Mn}$의 경우 1.67%(설계수질 기준), 2.59%(운영수질 기준), T-P의 경우 3.69%(설계수질 기준), 7.67%(운영수질 기준)로 다소 높게 나타났으나 하수처리장 운영에 미치는 영향은 거의 없을 것으로 판단된다. 또한, 고도처리공정인 산화부상분리 처리수 및 생물여과 처리수의 경우 연계부하율은 1% 내외로 고도처리설비 설치 시 과대 설비설치의 우려가 있다. 따라서 S하수처리장의 경제성 및 안정적인 운영을 고려할 경우 생물학적처리인 생물반응조를 거친 처리수를 연계하는 것이 바람직할 것으로 판단된다.