DOI QR코드

DOI QR Code

비선형 부하에서 커패시터 전류 궤환을 통한 고성능 UPS 설계

A Design of a High Performance UPS with Capacitor Current Feedback for Nonlinear Loads

  • 이우철 (한경대학교 전기공학과) ;
  • 이택기 (한경대학교 전기공학과, IT융합기술연구소)
  • 투고 : 2012.03.29
  • 심사 : 2012.04.23
  • 발행 : 2012.05.31

초록

This paper presents a digital control solution to process capacitor current feedback of high performance single-phase UPS for non-linear loads. In all UPS the goal is to maintain the desired output voltage waveform and RMS value over all unknown load conditions and transient response. The proposed UPS uses instantaneous load voltage and filter capacitor current feedback, which is based on the double regulation loop such as the outer voltage control loop and inner current control loop. The proposed DSP-based digital-controlled PWM inverter system has fast dynamic response and low total harmonic distortion (THD) for nonlinear load. The control system was implemented on a 32bit Floating-point DSP controller TMS320C32 and tested on a 5[KVA] IGBT based inverter switching at 11[Khz]. The validity of the proposed scheme is investigated through simulation and experimental results.

키워드

참고문헌

  1. S. K. Chung, D. S. Lee, "Steady-State Performance of Single-Phase PWM Inverters Using PLL Technique," The Transactions of The Korean Institute of Power Elelcronics, Vol. 9, No. 4, pp. 356-363, 2004. 8.
  2. J. H. Park, T. K. Roh, C. S. Kim, I. M. Ahn, J. I. Woo, "Design of Robust Double Digital Controller to Improve Performance for UPS Inverter", The Transactions of The Korean Institute of Power Elelcronics, Vol. 4, No. 2, pp. 116-127, 2003. 4.
  3. P. Maussion, M. Grandpierre, J. Faucher, and J.C. Hapiot,"Instantaneous Feedback Control of a Single-phase PWM Inverter with Nonlinear Loads by Sine Wave Tracking," IEEE-IECON 1989, pp. 130-135.
  4. del Viejo, M.; Alou, P.; Oliver, J.A.; Garcia, O.; Cobos, J.A, "Fast control technique based on peak current mode control of the output capacitor current," IEEE-ECCE2010, 2010, pp 3396-3402.
  5. K. P. Gokhale, A Kawanura, and R. G. Ho!I, "Dead beat microprocessor control of PWM inverter for sinusoidal output waveform synthesis," IEEE-PESC Conf Rec., 1985, pp. 28-36.
  6. T. Kawabata, T. Miyashita, and Y. Yamamoto, "Deadbeat control of three phase PWM inverter," IEEE Trans. on Power Electronics, vol. 5,no. 1, 1990, pp. 21-28. https://doi.org/10.1109/63.45996
  7. Michael J. Ryan, William E. Brumsickle, and Robert D. Lorenz, "Control Topology Options for Single-Phase UPS Inverters," IEEE Trans. on Industry Application, 1997, VOL. 33, NO. 2.
  8. D. K. Ku, J. K. Ji, G. S. Cha, J. H. Moon, "Design of Robust Voltage Controller for Single-Phase UPS Inverter", The Transactions of The Korean Institute of Power Elelcronics, Vol. 16, No. 4, pp. 317-325, 2011. 8. https://doi.org/10.6113/TKPE.2011.16.4.317
  9. Q. V. Tran, T. W. Chun, H.H. Lee, H. G. Kim, E. C. Nho, "Analysis of a Synchronizing PLL System for Single-phase Grid-tie Inverters", The Transactions of The Korean Institute of Power Elelcronics, Vol. 13, No. 6, pp. 447-452, 2008. 12.
  10. S. D. Finn, "A High Performance Inverter Technology, Architecture and Applications," IEEE-APEC Conf. Rec., 1993, pp. 556-560.
  11. M. J. Ryan and R. D. Lorenz, "A high-preformance sine wave inverter controller with capacitor current feedback and "Back-EMF" decoupling", Conf. Rec, IEEE-PESC, pp. 507-513, 1955.

피인용 문헌

  1. A Study on the Estimation of the Resonance Frequency for an Active Damping Technique of Grid Connected Converters vol.27, pp.1, 2013, https://doi.org/10.5207/JIEIE.2013.27.1.076
  2. The Study of the Circulation Current Control Scheme on Single Phase Inverter System vol.28, pp.2, 2014, https://doi.org/10.5207/JIEIE.2014.28.2.060