Abstract
The performance simulation of a desiccant rotor, which is a core component of a desiccant cooling system, was conducted on the basis of a theoretical solution of the heat and mass transfer process in the rotor. The simulation model was validated by comparing simulation results with experimental data; reasonable agreement was observed. The effect of the rotation speed on the performance of the desiccant rotor was investigated for various operation conditions: temperature (50 to $70^{\circ}C$), humidity ratio (0.01 to 0.02 kg/kg DA), and flow rate of regeneration air. The optimum rotation speed was determined from the maximum moisture removal capacity (MRC) of the desiccant rotor, and it was found to vary with the operation conditions. Further, the correlation for the optimum rotation speed was determined by regression analysis.
제습냉방시스템에서 주요 구성부품인 제습로터의 성능을 극대화 시키기 위한 방법으로 제습로터의 회전주기의 제어에 대한 연구를 수행하였다. 열과 물질전달의 과정을 모델화하여 얻은 수치해를 바탕으로 제습로터성능 시뮬레이션 프로그램을 구성하여, 재생공기 온습도, 풍량 등의 운전조건에 대하여 회전 주기에 따른 제습로터의 제습량을 구하였다. 성능 시뮬레이션 결과 검증을 위하여, 실험을 통해 측정된 값과 성능해석 모델을 이용하여 계산된 값을 비교함으로써 성능 시뮬레이션 모델의 타당성을 보였다. 각 운전조건에서 제습량이 최대가되는 제습로터의 회전주기를 최적 회전주기로 정의하였고, 회전주기를 고정(400s)할 때의 제습성능과 비교하여, 최적 회전주기제어가 제습성능에 미치는 영향을 분석하였다. 그리고 회귀분석법을 이용하여 재생온도, 외기상대습도, 풍량을 변수로 하는 최적 회전주기의 예측상관식을 개발하고 시뮬레이션 값과 비교하여 검토하였다.