Evaluation of Shell Geometry of the Natural Draught Cooling Tower using Linear Numerical Analysis

선형 전산해석을 이용한 자연 습식 냉각탑의 기하형상에 대한 평가

  • 노삼영 (한양대학교 건축학부) ;
  • 이상윤 (한양대학교 건축환경공학과) ;
  • 허동현 (한양대학교 건축환경공학과)
  • Received : 2012.07.18
  • Accepted : 2012.09.15
  • Published : 2012.09.15

Abstract

In the design procedure of the cooling tower the form-finding of the shell is the most important process, because the shape of the shell determines the sensitivity of dynamic behaviour of the whole tower against wind excitation. In engineering practice, geometric parameters of the shell are generally determined based on natural frequency analysis. 32 cooling tower shell geometries were selected through variation of the geometric parameters of an existing cooling tower shell. They were evaluated based on the first natural frequency. From the result three representative cooling towers are selected for the analysis of the structural behaviour by means of linear FE-method. As a result, a hyperbolic rotational shell with the small radius overall will yield the shell geometry with a higher first natural frequency and thus a wind-insensitive structure.

하이퍼볼릭 쉘로 구성된 냉각탑에서 쉘의 형상은 풍하중에 대하여 냉각탑 전체의 동적 거동에 민감하게 응답한다. 이에 따라 냉각탑 설계 시 기하형상의 결정은 매우 중요하며 일반적으로 고유진동수를 기반으로 하여 산정한다. 본 연구의 목적은 냉각탑 쉘의 구조적 거동에서 형상변수가 미치는 영향을 파악하고자 한다. 기존의 냉각탑 형상변수를 변화시켜 32개의 모델을 선정하였고 이를 1차 고유진동수를 기반으로 하여 분석한 후, 3개의 대표적인 형상을 선택하여 선형 해석을 수행하였다. 그 결과, 전체적으로 작은 반지름을 가지는 기하형상이 높은 1차 고유진동수를 나타내고 풍하중에 대하여 덜 민감한 시스템이 되는 것을 알 수 있었다.

Keywords

References

  1. 최창근, 노혁천. 철근콘크리트 냉각탑의 형상불완전에 의한 확률론적 거동. 한국전산구조공학회 논문집, Vol 13, No. 1, 2000, pp. 147-158.
  2. 민창식, 김생빈. R/C 쌍곡 냉각탑의 극한 거동. 대한토목학회 논문집, Vol 12, No. 4, 1992, pp. 59-70.
  3. D. Busch., R. Harte. and H.-J. Niemann. Study of a proposed 200m high natural draught cooling tower at power plant Frimmersdorf/Germany. Engng. Struct. Vol. 19, 1997.
  4. R. Harte. and W.B. Kratzig. Nonlinear Analyses of reinforced concrete shells as a preventive measure against damages, 40th Universary Congress of IASS, Madrid, 1999.
  5. S.Y. Noh, Harte, R., W.B. Kratzig and K. Meskouris. New design concept and damage assessment of large-scale cooling towers, Structural Engineering & Mechanics Vol 15, No. 1, 2003, pp. 53-70. https://doi.org/10.12989/sem.2003.15.1.053
  6. H. Beem., C. Koenke., U. Montag., W. Zahlten. Femas 2000 - Finite Element Moduls for General Structures Institute for Statics and Dynamics, Ruhr- University Bochum. User-Handbook Release 3.0., 1996.
  7. VGB - Guideline: Structural Design of Cooling Towers, VGB-Technical Committee, "Civil Engineering Problems of Cooling Towers", Essen, 1997.

Cited by

  1. Evaluation of Structural Performance of Natural Draught Cooling Tower according to Shell Geometry using Wind Damage Analysis - Part I : One-shell Geometry vol.16, pp.3, 2016, https://doi.org/10.9712/KASS.2016.16.3.067
  2. Evaluation of Structural Performance of Natural Draught Cooling Tower According to Shell Geometry Using Wind Damage Analysis – Part II : Two-Shell Geometry vol.17, pp.1, 2017, https://doi.org/10.9712/KASS.2017.17.1.049