A Study on the Circuit Breaker Transient Recovery Voltages on Large Commercial Customer using EMTP-RV Program

EMTP-RV를 이용한 대용량 전기설비의 차단기 TRV에 관한 연구

  • 조계술 (홍익대학교 대학원 전기공학과) ;
  • 최홍규 (홍익대학교 과학기술대학 전자.전기공학과)
  • Received : 2011.07.25
  • Accepted : 2011.08.31
  • Published : 2011.10.31

Abstract

In electric power system, the circuit breaker is not operated when the higher voltage then the rated TRV(transient Recovery Voltage) appeared in the circuit breaking, The TRV of a circuit breaker means the characteristics of reignition by the arc between two poles. and is decided by the value of connecting Impedance. In this paper we of carried out many kinds of experiments varying the types of bus, the types of installation, the length of installation between 22.9 [kV] level circuit breaker and MTR in general 154/22.9[kV] system, We also simulated the characteristics of TRV using EMTP-RV program. The suitability of TRV in assessed by Uc, RRRV(Rate of Rise of Recovery Voltage) which are defined by the international guide, IEC62271-100. The values of RRRV gained from the cable-made bus are 590[%] lesser than those from the NSPB-made bus respectively. So the triangled type is more rational in the aspect of TRV.

Keywords

References

  1. EMTP-RV(Electro Magnetic Transients Program Restructured Version), http://www.emtp.com.
  2. "High-voltage switchgear and controlgear : Part 100: Alternating-current circuit-breakers", IEC 62271-100, 2008.
  3. 한전표준규격, "교류차단기(ES-5925-0001)", 2007.
  4. 超高壓 電力系統 限流리액터 設置에 따른 遮斷器 過渡回復電壓(TRV) 解析, 박흥석, 忠南大學校 大學院,, 2004, p. 17.
  5. D.L. Swindler, P. Schwartz, P.S. Hamer, S.R. Lambert, "Transient Recovery Voltage considerations in the application of medium-voltage circuit breakers," IEEE Transaction on Industry Applications, vol. 33, No.2, March/April 1997, pp. 383-388. https://doi.org/10.1109/28.567999
  6. Greenwood, A., "Electrical Transients in Power Systems second edition", New York: Wiley, 1991.
  7. "IEEE Application Guide for Transient Recovery Voltage for AC High-Voltage Circuit Breakers," IEEE Std C37.011-2005 (Revision of IEEE Std C37.011-1994).
  8. 서훈철, 한후석, 한승우, "EMTP-RV를 이용한 개폐서지 모델링", 대한전기학회 추계학술대회논문집, 11, 2006.
  9. 정태영, 백영식, 정기석, 박지호, 서규석, "EMTP/RV를 이용한 22.9[kV] GIS 모델링과 과도회복전압 해석", 대한전기학회논문지, 59권, 7호, 2010년 7월.