Abstract
The co-generation system consisted of gas a turbine, a steam turbine, heat recovery steam generator and a heat exchangers for district heating was investigated in the present study. A back-pressure steam turbine (non-condensing type) was used. A partial load analysis according to the outdoor temperature in winter was conducted and optimal thermal load and power conditions was examined using the commercial computing software Thermoflex. As a result, under a constant thermal load, the power outputs of gas turbine and overall system increased as an outdoor temperature decreased. On the other hand, the reduction in exhaust gas temperature led to the decrease in output of steam turbine. Considering the portion of gas turbine in overall system in terms of the power output, it can be known that the tendency in power output of overall system was similar to that of the gas turbine.
본 연구에서는 가스터빈과 증기터빈, 열회수증기 발생 장치와 지역난방 열교환기로 열병합 발전 시스템을 구성하여 복수기가 없이 증기 터빈 중압단에서 추기된 증기와 배기 증기를 지역난방 열교환기의 열원으로 사용하는 추기 배압식을 적용하였다. 구성된 시스템에 대하여 필요로 하는 열부하량과 발전 출력 조건을 만족 시키기 위한 최적 설계 성능 해석을 하였으며, 이와 함께 겨울철 외기 온도 조건의 변화에 대한 시스템의 부분부하 해석을 하였다. 해석을 위해 상용 프로그램인 Thermoflex를 사용하였다. 시스템의 해석 결과, 기준 조건에서 수요처의 요구를 만족 시키는 최적 설계를 기준으로 각 외기 온도 변화에 대한 부분부하 성능 해석의 결과를 얻을 수 있었다. 그 결과 열부하량이 고정된 상태에서, 가스터빈과 전체 시스템의 출력은 외기온도가 감소함에 따라서 증가하였지만, 열원인 배기가스의 온도 감소로 인하여 증기터빈의 출력은 이와 반대로 감소하는 경향을 나타내었다. 그러나 전체 시스템에서 가스터빈의 차지하는 비중이 크기 때문에 전체 시스템의 출력의 경향은 가스터빈과 동일한 결과를 얻을 수 있었다.