Abstract
In this paper, among the active islanding detection techniques, the modified active frequency drift method was analyzed, which is relatively easy to apply to the single-phase grid-connected PV PCS. The existing designs for turbulences in these applications were empirically conducted, and do not have sufficient reliability and performance. Therefore, three application forms of the modified active frequency drift technique were modeled, based on which the proper magnitude of turbulence, which is the frequency acceleration component, was calculated. Using the results, the magnitude of and injection method for turbulence for ensuring the islanding detection performance and improving the output power quality were proposed, and they were verified via simulations and experiment to prove that the reliable islanding detection technique can be developed merely by measuring the basic output power quality, without the need for expensive islanding simulation equipment.
본 논문은 신 재생에너지원 중 태양광을 이용한 계통연계형 PV PCS의 단독운전 검출 성능을 극대화하고, 출력 전력의 품질 악화를 최소화 할 수 있는 개선된 능동 주파수 변이기법의 외란의 크기를 모델링, 시뮬레이션 및 실험을 통하여 검증하고, 이를 근거로 계통 보호 협조 및 안전을 위한 개선된 능동적 주파수 변이기법의 타당성을 검증하고자 한다.