Abstract
Recently luminous egress guide-lines are introduced for the fire safety of residents in the multi-use buildings such as Gosiwon. Little literature, however, on the quantitative and qualitative estimation for the egress performance of the luminous egress guide-lines can be found. This study carried out experimental investigations to evaluate the egress performance of the existing egress guide-lights and new luminous egress guide-lines. The results showed that both luminous egress guide-lines and egress guide-light satisfied the basic performance of KFI requirements. Under the 7 % smoke transmittance, however, luminous egress guide-lines showed 3 times longer visibility and less evacuation time than egress guide-lights. The evacuation density and smoke transmittance have significant effect on the evacuation time increase without the luminous egress guide-lines, however little effect with the installation.
고시원 등 다중이용업소의 경우 밀집화된 공간구조로 인해 화재 시의 인명위험도가 크게 부각됨에 따라 해당 건축물에 발광식 피난유도선의 설치를 도입함으로써 거주자의 피난안전성 확보를 꾀하고 있다. 그러나 자체발광식 피난유도선의 설치에 따른 피난성능 향상의 정량적, 정성적 평가에 대한 국내외 연구는 거의 없는 실정이어서, 본 연구에서는 기존의 피난유도등과 새로운 자체발광식 피난유도선에 대하여 다양한 피난시나리오에 따른 피난성능을 실험적으로 평가하였다. 실험결과는 피난유도선 및 유도등 모두 법적 기본 성능기준을 만족하였으나, 7 %의 낮은 연기투과율에서는 피난유도선의 식별거리가 유도등에 비해 약 3배 정도 뛰어난 식별성능을 나타내었다. 또한 연기투과율이 낮을수록 피난유도선쪽이 피난유도등에 비해 피난시간이 훨씬 짧은 것을 볼 때 성능 측면에서 피난유도선이 훨씬 효과적인 것으로 관측되었다. 피난유도선 미설치 시에는 피난시간 증가율이 피난밀도나 연기투과율에 크게 영향을 받았으나 피난유도선 설치시에는 별 영향을 받지 않는 것으로 나타났다.