Abstract
In this present study, a response modification factor for a lightweight steel panel-modular system which is not clarified in a current building code was proposed. As a component of the response modification factor, an over-strength factor and a ductility factor were drawn from the nonlinear static analysis curves of the systems modeled on the basis of the performance tests. The final response modification factor was then computed by modifying the previous response modification factor with a MDOF (Multi-Degree-Of-Freedom) base shear modification factor considering the MDOF dynamic behaviors. As a result of computation for the structures designed as a dual frame system, ranging from 2-story to 5-story, the value of 4 was estimated as a final response modification factor for a seismic design, considering the value of 5 as an upper limit of the number of stories.
본 연구에서는 복강판-모듈러 시스템과 같이 구조 기준에 명시되지 않은 새로운 시스템의 반응수정계수를 산정하는 절차를 제안하였다. 기본 개념은 구조성능 실험결과를 바탕으로 모델링 된 시스템의 비선형 정적 해석 곡선으로부터 세부 구성요소인 초과강도계수와 연성계수의 도출하고, 단자유도 시스템으로 간주하고 평가된 반응수정계수를 다자유도 동적 거동을 고려한 다자유도 밑면전단 수정계수로 수정하여 시스템의 최종적인 반응수정계수를 결정하는 것이다. 제안한 절차에 따라 이중골조시스템으로 설계된 2층부터 5층까지의 복강판-모듈러 시스템에 대해 평가한 결과, 최종적인 반응수정계수는 5층(층고 4m기준)을 복강판-모듈러 시스템의 적용 가능한 층수의 상한으로 하여 4로 결정하는 것이 타당할 것으로 판단하였다.