Abstract
Many electric poles in the softground have been collapsed due to external load. In this study, 10 types of tests were performed with variation of location, numbers and depths of anchor blocks as well as depth of poles to find horizontal earth pressure through full scale pull-out tests. The horizontal earth pressure increased with embedded depth of electric pole, and earth pressure of lower passive zone decreased. The deeper of anchor block, earth pressure of passive zone becomes less. lateral displacements showed differences depending on location, numbers and depth of poles. The bending is generated in the upper part at the initial load, but it moved to central part as load increased. The maximum horizontal displacement decreased to 1/1.6 at -0.5m depth of anchor block and 1.3m additional laying depth of poles into ground.
연약지반에 시공하는 많은 콘크리트전주가 외부하중으로 전도파괴가 발생하는데 본 연구에서는 실물인장실험을 실시하고 근가위치, 근가깊이, 근가개수, 전주근입깊이를 달리하면서 전주에 작용하는 수평토압을 분석하였다. 실물실험은 10가지 종류로 나누어 실험한 결과 수평토압은 전주 근입깊이가 클수록 커지고 하부수동영역이 길어지는 것으로 나타났다. 근가 설치위치가 깊을수록 하부수동영역 토압이 감소된다. 변위는 근가의 위치 및 수량, 전주기초의 근입깊이에 따라 뚜렷한 차이를 나타냈다. 초기하중 재하 시 상부에서 굴절된 양상을 보이다 점증하중에 따라 전주의 중앙부로 굴절의 양상이 전이되었다. 근가위치는 G.L(-) 0.5m인 상태에서 전주기초 깊이 1.3m를 추가로 근입 시 최대 수평변위는 약 1.6배의 감소를 보여 전주의 안정성이 증가하였다.