DOI QR코드

DOI QR Code

Integrated Protection Method for DC Railway Systems

통합형 직류철도 보호계전 방식

  • Received : 2010.07.07
  • Accepted : 2011.01.03
  • Published : 2011.02.01

Abstract

DC traction power system is operated ungrounded so that minimize the stray current. Because the stray current is still present, a rail potential is increased. The ground faults in the DC railway systems are usually detected by a potential relay(64P). Moreover, if the rail potential goes high in the ordinary operating state because of the traction load, the potential relay would be maloperated. A presented protective relaying algorithm that can identify exactly the faulted region and can distinguish a ground fault from the potential rising of the rail is presented in this paper. This paper presents simulation technique that is very similar to the real operation situation using PSCAD/EMTDC.

Keywords

References

  1. 이경구, 현용섭, 홍성래, 백재우, 민용호, "DC 급전계통의 디지털 보호계전기의 합리적 운용방안 검토", 한국철도학회 춘계학술대회 논문집, 2009.5월, pp946-958
  2. 양병남, 최신 전기철도공학, 2003, p.396-397
  3. 조웅기, 최규형, "직류전기철도 급전시스템에서 레일전위 해석을 위한 모델링", 조명․전기설비학회 논문지, 2010.6월, pp138-146
  4. 서울특별시지하철공사, "지하철 1-4호선 전력설비 정밀 안전진단 용역 보고서",2005.9월, pp 변전-63
  5. 정현기, 정존진, 안태풍, "지하철 직류보호계전시스템의 동작특성에 관한 연구", 한국철도학회 춘계학술대회 논문집, 2008.6월, pp449-463
  6. 윤임중, 이종우, "직류 전기철도에서의 레일전위 및 누설전류 해석을 위한 시뮬레이션 모델링", 한국철도학회 추계학술대회 논문집, 2008. 11월, pp196-201

Cited by

  1. An Analysis of Influence Between the Power Feeding Line Insulation and Negative Rail Potential for the DC Ground Fault Protection in the Rubber Wheel System vol.62, pp.4, 2013, https://doi.org/10.5370/KIEE.2013.62.4.577
  2. An Evaluation of Selective Grounding Fault Protective Relaying Technique Performance on the Ungrounded DC Traction Power Supply System vol.61, pp.12, 2012, https://doi.org/10.5370/KIEE.2012.61.12.1964