DOI QR코드

DOI QR Code

변압기용 절연유의 특성에 관한 실험적 연구

A study on an experimental basis a special character of insulating oil the use of a transformers

  • Kim, Sung-Dae (Department of Electrical Engineering, Tongmyong University) ;
  • Park, Il-Soo (Department of Refrigeration Engineering, Tongmyong University)
  • 투고 : 2011.10.20
  • 심사 : 2011.11.10
  • 발행 : 2011.11.30

초록

본 연구는 변압기 내부에 있는 절연유의 온도제어를 목적으로 열전소자인 펠티어 소자와 무전력 냉각장치인 Heat pipe를 이용한 다양한 시스템을 설계 제작하여, 절연유의 용량별 온도제어에 적용함으로써 최적의 시스템을 구현할 수 있었다. 실험을 통하여 $60^{\circ}C$ 이내의 상태에서는 Heat pipe 100 W + 펠티어 100 W의 조합형이 순수 Heat pipe 300 W보다 탁월한 성능을 확인할 수 있었다. 이를 통하여 조합형의 적정설계 방식이 우수하다는 것을 증명하고, 조합형을 사용함으로써 전기절약 효과와 수배전반의 보다 더 효율적인 관리에 기여하고자 한다.

This research is for temperature control of insulating oil inside the transformer. After I designed and manufactured various systems using Peltier element, which was thermal element, and Heat pipe, which was a cooling system, without electric power. The optimum system could be made by applying them to the temperature control for the insulating oil. I could verify that the combination type of Heat pipe 100 W+ Peltier 100W has a more outstanding capacity than pure Heat pipe 300 W within 60 degrees Celsius through experiments. Through this, I verify that the method of a proper design is prominent, and make an attempt at contribution to power saving effect and more effective control of Distributing board by using this combination type.

키워드

참고문헌

  1. Sadik, K. and Hongtan, L., "Heat Exchangers selection, rating and thermal design, 2ed.," CRC press, 2002.
  2. Incropera, F. P. and DeWitt, D. P., "Fundamentals of Heat and Mass Transfer, 4ed.," John Wiley & Sons, 1996.
  3. Lee, Y. S., Park, K. H., Ra, H. s. and Kang, H. K., " A Study on the Operating Characteristics of the Naphthalene Heat Pipe," Proceedings of the KSME Spring Annual Conference, pp. 2100-2104, 2005.
  4. Vogel, M., Xu, G., " Low Profile Heat Sink Cooling Technologies for Next Generation CPU Thermal Designs," ElectronicsCooling, Vol. 11, No. 1, pp. 20-26, 2005.
  5. N. J. Lamfon, M. Akyurt. and Y. S. H. Najjar, " Waste Heat Recovery Using Looped Heat Pipers for Air Cooling," Heat Recovery Systems & CHP, Vol. 4, pp. 365-376, 1994.
  6. S. Chengming, X. Mingdal and C. Yuanguo, "Analysis of Three-Fluid Separate Type Heat Pipe Exchanger," Heat Recovery Systems & CHP, Vol. 12, No. 4, pp. 317-322, 1992 https://doi.org/10.1016/0890-4332(92)90027-F