초록
A bushing is very important because it must supply the high voltage to the power equipment. Generally, the surface of bushing is contaminated with rain, dust, salt and others. A bushing with contaminations at air are serious problem in insulation. Therefore, it is important to understand the inspection and diagnoses of the safety. The ultra-violet rays(UV) camera has attracted interest from the view point of easy judgement. In this paper, we will report on the corona discharge characteristics on bushing model with contaminations. Also, UV images of discharge in air are analyzed using prototype UV camera of Korea. These results are studied at both AC and DC voltage under a non-uniform field.