Abstract
This study performed the prediction about the indoor contaminant's diffusion characteristics which can be affected by the mechanical ventilation system on a training ship. The results are as followings. It is clear that the contaminants are spread to most of the indoors, regardless of the contamination beginning zone. About 65~100 minutes later, the contaminant densities of whole indoor zones are evaluated as clean. Comparing the contamination beginning zone being located at higher deck(scenario A) to the contamination beginning zone being located at lower deck(scenario B), although the contaminant density by scenario A is 10 times higher than that by scenario B, the number of contaminated zones are 50% less. The contaminant densities are evaluated as to be rapidly decreased when the outside air induction ratio against design volume is over 75%.
본 연구는 기계식 환기장치에 의한 선박 선실 내의 환경오염물질 확산특성을 파악한 것으로, 연구성과는 다음과 같다. 오염발생 선실 내에서는 오염발생 35분 경과 후 오염물질이 대부분 제거되었고, 신선외기 도입율 변화에 따른 영향은 무시할 수 있었다. 오염원 선실에 인접한 선실의 오염물질 제거시간은 65분~100분 정도로 신선외기 도입율에 따라 차이가 발생했다. 상부 데크에 오염원 선실이 있는 경우가 하부 데크에 오염원 선실이 있는 경우에 비해, 오염농도는 10배 정도 높지만, 대표 공간 중 오염된 공간의 수는 오히려 1/2에 불과했다. 그러나 전체공간을 대상으로 한 평가에서는, 상부 데크에서 오염물질이 발생한 경우에는 Upper 데크 이상 상부 데크 내 공간의 50% 이상이 평가기준 0.001%, 0.01%, 0.1% 일 때 오염될 것으로 예측되었고, 하부 데크에서 오염물질이 발생하는 경우에는 하부 데크를 중심으로 오염공간이 많지만 오염판단기준 0.01%일 때에는 Shelter 데크 이상의 상부 데크에서도 오염선실이 나타났다. 한편, 신선외기 도입량 변화에 따른 오염농도 및 오염공간 비율을 분석한 결과 설계용량 대비 75% 이상의 외기가 도입될 때 선실 내 오염수준이 낮아지는 것으로 평가되었다.