DOI QR코드

DOI QR Code

삼인산 나트륨과 아질산 나트륨에 의한 탄소강 부식방지 특성 연구

Study on The Corrosion Inhibition Characteristics of Carbon Steel by Sodium Phosphate And Sodium Nitrite

  • 문전수 (전력연구원 녹색성장연구소) ;
  • 이재근 (전력연구원 녹색성장연구소)
  • Moon, Jeon-Soo (Green Growth Laboratory, Korea Electric Power Research Institute) ;
  • Lee, Jae-Kun (Green Growth Laboratory, Korea Electric Power Research Institute)
  • 투고 : 2010.05.25
  • 심사 : 2010.06.17
  • 발행 : 2010.06.01

초록

Sodium nitrite is widely used as one of the popular corrosion inhibitors for the protection of ferrous metal in closed cooling water system, such as a diesel engine and a chiller. The optimum treatment conditions are studied through laboratory tests using linear polarization resistance (LPR) technique. Corrosion rate of the carbon steel electrode could be maintained less than $2.5{\times}10^{-3}$ mmpy in the test condition of 500 ppm as ${NO_2}^-$, 200 ppm as $Cl^-$, $70^{\circ}C$ and pH 6.8. The pH control is confirmed not to be an important factor in the protection of carbon steel by sodium nitrite inhibitor. The addition of tolyltriazole was needed for the protection of the copper alloy in the sodium nitrite treatment system.

키워드

참고문헌

  1. V. A. Kumari, K. Sreevalsan, and M. A. Shibli, Corrosion Prevention & Control, p. 83 (2001).
  2. K.N. Mohana and A.M. Badiea, Corros. Sci., 50. 2939 (2008). https://doi.org/10.1016/j.corsci.2008.07.002
  3. Closed Cooling Water Chemistry Guideline, Revision 1. EPRI, Palo Alto, CA, TR-107396.3 (2004).
  4. A.A. Moccari, Materials Performance, p. 54 (1999).
  5. B.P. Boffard, Fundamentals of Cooling Water Treatment, Calgon Corp., PA.