DOI QR코드

DOI QR Code

온수분배기용 유량제어밸브의 개발

Development of Flow Control Valves for Hot Water Distribution Manifolds

  • 권우철 (한양대학교 대학원 기계공학과) ;
  • 윤준용 (한양대학교 기계정보경영공학부) ;
  • 유선학 (신한콘트롤밸브(주))
  • 투고 : 2009.06.01
  • 심사 : 2010.05.31
  • 발행 : 2010.08.01

초록

The developed control valves, installed on the hot water distribution manifolds for the floor heating system, consist of the balancing valves and the shut-off valves. The balancing valve was designed to improve the flow control performance and to reduce the noise emitted from the valve by modification of the general V port. The port of the shut-off valve was designed with two ceramic plates, working by rotating upper plate, to improve the duration and to reduce the noise. For the evaluation of the new valves, the flow rate was measured and noise level test was carried out. The test results showed that the error of the flow rate accuracy test for the flow balance of each manifold circuit was less than ${\pm}3%$ and the noise level was less than 35 dB(A).

키워드

참고문헌

  1. 권우철, 윤준용, 이병휘, 2006, “난방용 온수분배기의 성능 평가 방법,” Proceedings of The Fourth National Congress on Fluids Engineering, August 23-25, 2006, Kyungju, Korea, pp. 1169-1172.
  2. 권우철, 강승덕, 유선학, 윤준용, 2008, “난방용 시스템온수분배기의 소음 절감 방법에 관한 연구,” 2008 유체기계 연구개발 발표회 논문집, 제주, pp. 623-624.
  3. 조성환, 2005, “온수분배기의 유량조절 및 밸런싱,” 설비저널, 제34권, 제8호, pp. 49-55.
  4. 윤준용, 권우철, 2007, “Y 스트레이너형 자동 정유량 조절 밸브의 개발,” 유체기계저널, 제10권, 제1호, pp. 49-55. https://doi.org/10.5293/KFMA.2007.10.1.049
  5. 이태원, 김용기, 2004, “공동주택에서의 효과적인 난방열량제어 관리방안,” 설비저널, 제33권, 제2호, pp. 11-21.
  6. W. L. Scull, "Control valve noise rating: predition versus reality," ISA Handbook of Control Vlave 2nd edition, pp. 45-133.
  7. 한국산업규격, “KS B 2304-밸브의 검사통칙,” 한국표준협회.
  8. Bruce R. Munson, Donald F. Young, and Theodore H. Okiishi, "Fundamentals of fluid mechanics," 2nd edition, WILEY.