Characteristics of Precise Temperature Control of Industrial Cooler on Thermal Load

산업용 냉각기의 열부하 변화에 대응한 정밀온도제어 특성

  • Received : 2010.03.02
  • Accepted : 2010.04.01
  • Published : 2010.04.30

Abstract

Recently, technical trend for machine tools is focused on enhancement of speed and accuracy. High speedy processing causes thermal and structural deformation of objects from the machine tools. Water cooler has to be applied to machine tools to reduce the thermal negative influence with accurate temperature controlling system. Existing On-Off control type can't control temperature accurately because compressor is operated and stopped repeatedly and causes increment of power consumption and decrement of the expected life of compressor. The goal of this study is to minimize temperature error in steady state. In addition, control period of an electronic expansion valve were considered to increment of lifetime of the machine tools and quality of product with a water cooler. PI controller is designed using type of hot-gas bypass for precise control of temperature. Gain of PI is decided easily by method of critical oscillation response, excellent performance of control is shown with 4.24% overshoot and ${\pm}0.2^{\circ}C$error of steady state. Also, error range of temperature is controlled within $0.2^{\circ}C$although disturbance occurs.

Keywords

References

  1. Beak, S. M. et al., 2009, "Characteristics of Temperature Control by Hot-gas Bypass Flow Rate on Industrial Water Cooler", The Korean Society of Marine Engineering, Vol. 33, No. 8, pp. 55-62.
  2. Lee, S. W., Yeom, H. K., 2008, "Performance of thermal error controller to minimize thermal deformation of machine tools", Proceeding of Korean Society for Precision Engineering(spring), pp. 376-380.
  3. Lee, S. W. and Lee, C. W., 2007, "Assessment capability of oil cooler with hot-gas", Proceeding of Korean Society for Precision Engineering, No. 6, pp. 459-460.
  4. J. H. Choi et al., 2009, "Performance Characteristics of Cooler Controled Capacity Using Hot-gas Bypass", Int. Symp. on Convective Heat and Mass Transfer in Sustainable Energy, Vol. 2, pp. 502-505.
  5. Yaqub. M, Zubair S. M., Jameel-ur-Rehman Khan, 2000, "Performance evaluation of hot-gas bypass capacity control scheme for refrigeration and air-conditioning systems", Energy, Vol. 25, pp. 543-561. https://doi.org/10.1016/S0360-5442(00)00004-9
  6. Yaqub. M, Zubair S. M., Jameel-ur-Rehman Khan, 2000, "Performance evaluation of hot-gas bypass capacity control scheme for refrigeration and air-conditioning systems", Energy, Vol. 25, pp. 543-561. https://doi.org/10.1016/S0360-5442(00)00004-9
  7. Byun J. Y. et al., 2009 "Precise Temperature Control of Oil Cooler with Hot-gas Bypass", The Korean Society for Power System Engineering, KSPSE The 2009 Spring Conference, pp. 141-146.
  8. Byun J. Y., Jeong J. M., and Jeong S. K.. 2009 "Hot-gas bypass control by PI logic for precise temperature of oil coolers with an electronic expansion valve", ISAMPE 2009, pp. 272-276.