Abstract
The smoke density and noxious gas for phenol foam and polyurethane foam were measured according to test methods in ASTM E 662 and KS F 2271. It was observed that phenol foam had the possibility of application for sandwich panel and board compared with polyurethane foam. In the experimental results, phenol foam showed comparatively excellent property than polyurethane foam in smoke density and noxious gas. The polyurethane foam showed comparatively high smoke density and didn't meet the evaluation standard of noxious gas in KS F 2271. From the experimental results of smoke density and noxious gas, it can be said that phenol foam has both comparatively good safety and high possibility of application than polyurethane foam in the building fire of sandwich panel structure because of lower smoke density and noxious gas.