DOI QR코드

DOI QR Code

The Comparison and Analysis about Earth System based on IEC60364

IEC 60364 기반 접지계통 비교 분석

  • 정진수 (한국전기안전공사 전기안전연구원) ;
  • 한운기 (한국전기안전공사 전기안전연구원) ;
  • 김오환 (한국전기안전공사 전기안전연구원) ;
  • 김재철 (한국전기안전공사 전기안전연구원)
  • Published : 2010.01.31

Abstract

This paper describes the analysis of loop impedance characteristics by impedance alteration of protective conductors and operating characteristics of electric leakage circuit breaker by each earth systems(TT system, TN-S system and TN-C system) in IEC 60364. As a result, loop Impedance was affected by resistance & inductance. The current& voltage characteristics about earth system were identified that the TN-S system was high fault current & low touch voltage. TN-C system was almost same the TN-S system but TT system was low fault current & high touch voltage.

본 논문에서는 IEC 60364에서 제시하고 있는 접지계통(TT접지계통, TN-S 접지계통 및 TN-C)의 누전차단기 동작특성 및 보호도체의 임피던스변화에 따른 Loop Impedance 특성분석을 실시하였다. 분석결과 Loop Impedance의 경우 저항성분과 인턱턴스성분에 영향을 받는 것으로 나타났다. 접지계통별 전류 전압특성은 TN-S 접지계통 및 TN-C 접지계통의 경우 사고전류가 높고 접촉전압이 낮은 특성을 나타낸 반면 TT 접지계통의 경우 사고전류는 낮고 접촉전압이 높게 나타남을 확인하였다.

Keywords

References

  1. 한국전기안전공사, “IEC60364 건축전기설비 해설서”, 2006. 11.
  2. 정진수, 한운기, “국제 건축전기설비 기준 (IEC60364)의 국내 적용 실태조사”, 한국조명전기설비학회 논문집, Vol. 22, No. 10, pp. 134-140, 2008.
  3. 산업자원부, “전기설비 기술기준 및 판단기준”, 2006. 10.
  4. British Standards, “Requirements for Electrical Installation”, 2008.
  5. IEE, “Earthing and Bonding”, 2004.

Cited by

  1. Analisys about the Earth Fault Characteristics in the Wireless Power Transmission System of the Electric Vehicle vol.28, pp.12, 2014, https://doi.org/10.5207/JIEIE.2014.28.12.013