A Study on Outdoor Acoustic Noise for HVDC Converter Station

HVDC 변환소의 옥외소음 분석

  • Received : 2010.05.31
  • Accepted : 2010.10.21
  • Published : 2010.12.31

Abstract

HVDC converter station consists of a number of equipment such as converter transformer, ac filter, thyristor valve and so on. They can be acoustic noise sources. In this paper, we analyzed the simulation results of the outdoor acoustic noise for HVDC converter station. It shows that maximum noise level in boundary of HVDC converter station exceeds regulation value. The main factors in generating maximum noise level are ac filter and converter transformer. Then we applied some soundproof countermeasures in HVDC converter station. Shielding wall is enough to reduce transformer noise level but not enough to reduce ac filter noise level. In case of ac filter, soundproof building is effective in satisfying noise level regulation in boundary of HVDC converter station. In addition, we also studied effects of season, soundproof woods, ground.

Keywords

References

  1. ISO 9613-1: Acoustics - Attenuation of sound during propagation outdoors - Part 1: Calculation of the absorption of sound by the atmosphere, 1993.
  2. ISO 9613-2: Acoustics - Attenuation of sound during propagation outdoors - Part 2: General method of calculation, 1996.
  3. SNAME TR 3-37: Design guide for shipboard airborne noise control, 1983.
  4. NEBB (National Environmental Balancing Bureau): Sound and Vibration - Design and Analysis, 1994.
  5. L.L. Beranek and I.L. Ver: Noise and vibration control engineering, John Wiley & Sons, Inc. 1992.
  6. Report of Working Group14.26 HVDC Station audible noise, CIGRE 2002.
  7. CreaTech: ENPro Version 3.1 user manual, 2001.
  8. 소음 진동관리법 시행규칙.