DOI QR코드

DOI QR Code

Characteristics of Ultra High Frequency Partial Discharge Signals from Metallic Particle Defected Oil-paper Insulation in Transformer

변압기 절연지 표면 금속 이물질 방전에 의한 극초단파 신호특성

  • 윤진열 (한국전력공사 전력연구원 송배전연구소) ;
  • 주형준 (한국전력공사 전력연구원 송배전연구소) ;
  • 구선근 (한국전력공사 전력연구원 송배전연구소) ;
  • 박기준 (한국전력공사 전력연구원 송배전연구소)
  • Received : 2009.08.19
  • Accepted : 2009.09.23
  • Published : 2009.10.01

Abstract

This paper was provided to help in detecting defects in power transformer. For this purpose, a partial discharge cell was designed and manufactured as a discharge source to simulate particle defected paper-oil insulation in power transformer. Experimental set-up for measuring PD signals was described. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and pattern of PRPD(Phase Resolved Partial Discharge) of partial discharge signals were examined and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the substation faults.

Keywords

References

  1. G. Wanninger, “Apparent charge measurement in GIS by modern diagnostic methods”, Eur. Trans. Elect. Power, Pt. 4, Vol. 7, p. 251, 1997.
  2. M. D. Judd and O. Farish, “FDTD simulation of UHF signals in GIS”, Proc. 10th Int. Symp. on High Voltage Engineering Montreal, Vol. 6, 1997.
  3. 윤진열, 박기준, 구선근, “GIS 부분방전 검출 기술연구”, 한국전력공사 전력연구원, TR 98J2002.407. 2002.
  4. 윤진열, 박기준, 구선근, “GIS 고장예방을 위한 UHF 부분방전 신호해석기술 연구”, 전력산업연구개발사업 최종보고서, 한국전력공사전력연구원, 2005.
  5. K. Raja, F. Devaux, and S. Lelaidier, "Recognition of discharge sources using UHF PD Signatures", IEEE Electrical Insulation Magazine, Vol. 18, Iss. 5, p. 8, 2002.
  6. Werle, P., Borsi, H., and Gockenbach, E., “Diagnosing the insulation condition of dry type transformers using a multiple sensor partial-discharge-localization technique”, Electrical Insulation, 2002. Conference Record of the 2002 IEEE International Symposium on, p. 166, 2002.
  7. Gockenbach, E., “Partial discharge detection and localization in power transformers”, Electrical Insulation and Dielectric Phenomena, 2004. CEIDP '04. 2004 Annual Report Conference on, p. 466, 2004.
  8. Shen, Z. B. and El-Saadany, E. F., “Localization of partial discharges using UHF sensors in power transformers”, Power Engineering Society General Meeting, 2006.
  9. J. Fuhr, “Procedure for identification and localization of dangerous PD sources in power transformers”, Dielectrics and Electrical Insulation, IEEE Transactions on, Vol. 12, Iss. 5, p. 1005, 2005. https://doi.org/10.1109/TDEI.2005.1522193
  10. H. Xiaoyun, L. Yifeng, and L. Yi, “Study of PD detection and location by means of acoustic measurements transformer”, Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on, Vol. 2, p. 753, 2000.
  11. Homaei, M., Mazhab Jafari, A., and Akbari, A., “Investigating suitable features for partial discharge localization in power transformer”, Condition Monitoring and Diagnosis, 2008. CMD 2008. International Conference on, p.923, 2008.
  12. Jafari, A. M., Akbari, A., Mirzaei, H. R., Kharezi, M., and Allahbakhshi, M., “Investigating practical experiments of partial discharge localization in transformers using winding modeling”, Dielectrics and Electrical Insulation, IEEE Transactions on, Vol. 15, Iss. 4, p. 1174, 2008. https://doi.org/10.1109/TDEI.2008.4591240
  13. Agoris, P., Cichecki, P., Meijer, S., and Smit, J. J., "Building a transformer defects database for UHF partial discharge diagnostics", Power Tech, 2007 IEEE Lausanne, p. 2070, 2007.
  14. Massingue, F., Meijer, S., Agoris, P. D., Smit, J. J., and Lopez-Roldan, J., "Partial discharge pattern analysis of modeled insulation defects in transformer insulation", Conf. Record of the 2006 IEEE Int. Symp. on Electrical Insulation 2006, p. 542, 2006.
  15. G. P. Cleary and M. D. Judd, "UHF and current pulse measurements of partial discharge activity in mineral oil", IEE Proc.-Sci. Meas. Technol., Vol. 153, No. 2, p. 47, 2006. https://doi.org/10.1049/ip-smt:20050103
  16. Aschenbrenner, D., and Kranz, H.-G., "On line PD measurements and diagnosis on power transformers", IEEE Trans. on Dielectrics and Electrical Insulation, Vol. 12, No. 2, p. 216, 2005. https://doi.org/10.1109/TDEI.2005.1430392
  17. Jongen, R. A., Morshuis, P., Meijer, S., and Smit, J. J., "Identification of partial discharge defects in transformer oil", 2005 Ann. Report Conf. on Electrical Insulation and Dielectric Phenomena 2005, p. 565, 2005.