In order to increase the capacity of the superconducting fault current limiter(SFCL), the current and voltage grades of the SFCL must be increased. As a method for the increase of the current and voltage grades of the SFCL, we compared the various characteristics between the flux-lock type SFCL "With three superconducting units connected in series and the transformer type SFCL using the transformer with three secondary circuits. One of three superconducting units had not quenched in the flux-lock type SFCL. Therefore, the unbalanced power burden happened because of the voltage difference generated by unbalanced quenching between the superconducting units. In the meantime, the three superconducting units were all quenched in the transformer type SFCL using the transformer, and the voltage difference generated between the superconducting units was decreased. Therefore, the difference of critical characteristics was complemented by distribution of fault current in accordance with the turn's ratio between primary and secondary windings. The unbalanced power burden of the superconducting units was reduced due to flux-share between the superconducting units in the transformer. In conclusion, the capacity increment of the SFCL using a transformer was easier due to equal distribution of voltages generated by simultaneous quench of the superconducting units. We think that the characteristics is improved more because of the decrease of saturation in the iron core if the secondary winding is increased in the SFCL using the transformer.

Keywords

References

  1. B. Gromoll, G. Ries, W. Schmidt, H.-P. Kraemer, B. See bacher, B. Utz, R. Nices, H.-W. Neumueller, E. Baltzer, and B. Heismann, "Resistive type fault current limiters with YBCO thin film-100 KVA functional model.", IEEE, vol. 9. no. 2, pp. 656-689. June 1999 https://doi.org/10.1109/77.783381
  2. K. Kajikawa, K. Kaiho, N. Tamada, and T. Onishi, "Design and current limiting simulation of magnetic shied type superconducting fault current limiter with High-Tc superconductors", IEEE, vol. 32, no. 4, pp. 2667-2670, july 1996 https://doi.org/10.1109/20.511423
  3. H. R. Kim, H. S. Choi, H. R. Lim, and O. B. Hyun, "Quench distribution in superconducting fault current limiters at various voltae", Cryogenics, vol. 41, pp. 275-280, April 2001. https://doi.org/10.1016/S0011-2275(01)00105-9
  4. H. S. Choi, O. B. Hyun, and H. R. Kim, "Quench characteristics of resistive superconducting fault current limiters based on YBa2Cu307 films", Physica C, vol. 351, pp. 415-420, April 2001. https://doi.org/10.1016/S0921-4534(00)01632-4
  5. Sung-Hun Lim, Hyo-Sang Choi, Byoung-Sung Han, "The improved htsteresis charcterristics of flux-lock type SFCL using third winding", Physica C, Vol. 406, pp. 37-45, july 2004 https://doi.org/10.1016/j.physc.2004.02.177
  6. S. H. Lim, T.H. Han, Y.S. Cho, H.S. Choi, B.S. Han, Su-Won Lee, "Quench characteristics of HTSC elements in integrated three-phase flux-lock type SFCL according to ground-fault", Physica C, Vol. 463-465, pp. 1198-12031, October 2007 https://doi.org/10.1016/j.physc.2007.03.458
  7. S. H. Lim, H. S. Choi, B. S. Han, "Fault current limiting characteristics due to winding direction between coil 1 and coil 2 in a flux-lock type SFCL" Physica C, Vol 416, pp 34-42, November 2004 https://doi.org/10.1016/j.physc.2004.08.019
  8. S. B. Chung, H. M. Park, H. S. Choi, "Improvement of quench properties of a flux-lock type superconducting fault current limiter by the connection method of YBCO elements" KIEE, Vol. 56, pp.37-44, March 2007
  9. S. H. Lim, " Fault Current Waveform Analysis of a Flux-Lock Type SFCL According to LC Resonance Condition of Third Winding" KIEE, Vol. 3, pp. 213-217, June 2008 https://doi.org/10.5370/JEET.2008.3.2.213