Abstract
This paper presents the ground surface potential profiles and hazard voltages around the metallic structure connected to a small-sized model ground electrode. Because it is very difficult to draw valid conclusions concerning a general grounding problem from actual field data, scale model tests can be used to determine the touch and stop voltages and surface potential profiles around ground electrode. In this work, a hemispherical vessel with a diameter of 1,100[mm] was employed to simulate uniform soil. As a result, the ground surface potential around the ground electrode was significantly raised In particular the ground surface potential at the just upper point of ground rod was higher than other points. When the buried depth of ground rod is increased, the ground surface potential and step voltage were lowered but the touch voltage was elevated.
본 논문은 축소형 모델 접지전극이 접속된 금속제 구조물 주변의 대지표면전위분포와 위험전압에 대하여 기술하였다. 접지에 관련된 문제를 실제 현장데이터로부터 적정한 결론을 도출하기는 매우 어려우므로 접지전극 주변의 전위분포와 접촉전압, 보폭전압의 산정에 축소형 모델시험을 사용한다. 본 연구에서는 균질토양을 모의하기 위해 직경이 1,100[mm] 반구형 용기를 사용하였다. 실험결과, 접지전극 주변의 대지표면전위는 매우 높게 나타났으며, 특히 접지전극의 직상부의 대지표면전위는 다른 위치에 비해 높게 나타났다. 접지전극의 매설깊이가 증가함에 따라 대지표면전위와 보폭전압은 낮아지지만 접촉전압은 높아지는 것으로 나타났다.