가스충전소에서 작업복의 정전기 안전관리에 관한 연구

A Study on the Safety Management of the Electrostatic in Working Clothes at the Gas Station

  • 이금환 (서울산업대학교 에너지환경대학원) ;
  • 정재희 (서울산업대학교 안전공학과)
  • Lee, Geum-Hwan (The Graduate School of Energy and Environment, Seoul National University of Technology) ;
  • Chung, Jae-Hee (Department of Safety Engineering, Seoul National University of Technology)
  • 발행 : 2009.12.31

초록

In order to prevent fire and explosion due to the electrostatic discharge at the Gas Station etc. This result will be applied to standard in the future. Wearing the non-electrostatic removing wear, Charged voltage of human body is 3,980V(MIE is approximately 0.79mJ). There is a possibility of fire explosion because the MIE of LP gas is 0.25mJ. In accordance with using period(whasing times), Charged voltage is shown that propensity is increased. Electrostatic charge amount is upper standard($0.6{\mu}$C) of the hazard of electrostatic removing wear. There is a possibility of fire and explosion. Therefore, countermeasure and management are needed about gas station worker.

키워드

참고문헌

  1. 충전시설 안전관리, 한국가스안전공사 가스안전교육원 2007
  2. World LP Gas Association 'Autogas incentive policies'
  3. 조영두 외 '한국의 LPG 충전소에 있어서 작업복의 정전기에 의한 화재 및 폭발 위험성에 관한 연구', KIGAS, Vol. 4, No. 4, December, 2000
  4. 이덕출.정재희 공역, '정전기재해와 장해 방지', 성안당, 1996
  5. 정재희 외 '천연가스 사용시설에서의 정전기 발생과 방지에 관한 연구', 한국가스공사 연구개발원, 2000
  6. 김두현 외, '최신전기안전공학', 신광문화사, 2008
  7. 장갑식, '섬유의 방오가공 기술', FITI 시험연구소
  8. Jean Cross and Donald Farrer 'Dust Explosion', p. 69, 1990
  9. 노동성산업안전연구소, '정전기안전지침', pp. 4, pp. 43-45, 1988
  10. Report on the risk of static ignition during vehicle refuelling, The Institute of Petroleum, UK, 2001
  11. KS '섬유 시험에 대한 가정 세탁과 건조 과정' KS K 6330
  12. KS '직물 및 편성물의 대전성 시험 방법' KS K 0555
  13. KS '정전기 대전 방지 작업복' KS K 7807