An Experimental Study of Operating Characteristics on Fouling Auto Removal Apparatus of Multi Pass Type Heat Exchanger using Ejector

이젝터를 이용한 다관식 열교환기 파울링 자동제거장치의 구동특성에 관한 실험적 연구

  • 김재돌 (동명대학교 공과대학 냉동공조공학과)
  • Published : 2009.12.31

Abstract

The experiment was performed to check operating characteristics of fouling auto removal apparatus for multi pass type heat exchanger using ejector. The results showed as following. The ejector suction flow rate increased with the head of operating pump of ejector. Proper suction flow rate showed $7.2{\sim}10.2m^3/h$ for ball collection in case of pump head 35~50m. The head of ejector outlet pipe is below 4.1m in case of 40m, the head of operating pump of ejector to confirm ejector suction flow rate 8.4m3/h. Lattice space of ball separator is allowed 6~10.3mm in ranges of ball diameter are 15~25mm and when mass flow of cooling water is 3.0m/sec. Average of passing time of balls is 1.2~2.8sec depend on the velocity of flow and the size of balls.

Keywords

References

  1. 김재돌, 2009, "이젝터를 이용한 다관식 열교환기 자동세정장치의 구동특성에 관한 실험적 연구", 대한기계학회, 2009년도 춘계학술대회 논문집, pp. 328-333.
  2. 김재돌, 설원실, 2009, "열교환기 파울링 자동제거장치 최적화를 위한 세정볼 실험에 관한 연구", 한국동력기계공학회, 2009년도 춘계학술대회 논문집, pp. 244-249.
  3. 김재돌, 설원실, 윤정인, 2004, "쉘앤튜브식 열교환기 세정 자동화 기술", 냉동.공조공학, 제 23권, 제 4호, pp. 59-72.
  4. GRETH, 1992, "Fouling Mechanisms", France seminar
  5. 이윤표, 2001, "냉동기에서 Fouling의 영향", 냉동.공조공학, 제 20권, 제 2호, pp. 19-26.
  6. Frank P. Incropera, David P. Dewitt, 1990, "Fundamentals of Heat and Mass Transfer", John Wiley and Sons.
  7. Kern, D. Q. and Seaton, R. E., 1979, "A theoretical analysis of thermal surface fouling", Brit. Chem. Eng., Vol. 4, No. 5, pp. 258-262.
  8. C. B. Pranchal, 1995, "Fouling Mitigation of Industrial Heat-Exchange equipment".