Abstract
The application of a large power transformer into a power distribution system was inevitable due to the increase of power demand and distributed generation. However, the decrease of the power transformer‘s impedance causes the short-circuit current of the power distribution system to increase and thus, the higher short-circuit current exceeds the cut-off ratings of the protective devices such as a circuit breaker. To solve these problems, several countermeasures have been proposed to protect the power system effectively from the higher fault current and the superconducting fault current limiter (SFCL) has been expected to be the promising countermeasure. However, the current limiting effect of SFCL including its bus voltage drop compensation depends on SFCL's application location in a distributed power system. In this paper, the current limiting and the bus-voltage drop compensating characteristics of the SFCL applied into a power distribution system were studied. In addition, the quench and the recovery characteristics of the SFCLs in each location of the power distribution system were compared each other.
배전계통에서 전력수요의 증가와 분산전원의 증가로 대용량 변압기의 적용이 불가피하게 되었다. 하지만, 대용량 변압기로 교체할 경우 배전계통에 고장발생시 고장전류의 크기가 증가되어 기존에 설치된 차단기 및 보호기기의 차단용량 초과로 인해 교체에 따른 경제적 비용 상승이 우려된다. 따라서, 대용량 변압기의 교체시 고장전류 증가 문제를 해결하기 위한 방안 중 하나로 초전도한류기를 설치하는 방안을 검토하고 있다. 하지만, 초전도한류기는 도입위치에 따라 ��치 발생 시 초전도한류기의 저항 크기가 다르게 되며, 이로 인해 고장전류 제한효과가 다르게 되며 기존의 보호 장치들의 동작에 영향을 주게 된다. 본 논문에서는 모의 배전계통에 초전도한류기를 적용하였을 경우 도입위치에 따라 전류제한효과를 포함하여, 모선 전압강하, 고장제거에 따른 초전도한류기의 회복특성을 실험을 통해 비교 분석하였다.