DOI QR코드

DOI QR Code

Comparison of Arc Control Ability as a Function of Configuration of Spiral Type VI Contacts by Measuring Arcing Time

아크지속시간 측정을 통한 나선형 VI 전극의 전극배치에 따른 아크제어 성능비교

  • 김병철 (충북대학교 전기공학과 전기재료연구실) ;
  • 박홍태 (LS산전(주) 전력연구소) ;
  • 오일성 (LS산전(주) 전력연구소) ;
  • 임기조 (충북대학교 전기공학과 전기재료연구실)
  • Published : 2009.02.01

Abstract

One of the purposes of arc control is to change its state to the diffuse state before current zero as soon as possible. This can provide optimal conditions for full extinction of arc by minimizing the quantity of residual plasma between contacts near current zero. TRV(transient recovery voltage) occurs at current zero at the same time with current interruption. If there is substantial residual plasma near current zero it can cause 'post arc current' by the interaction of its conductance with TRV. In this paper, arc control ability as a function of configuration of spiral type VI contacts was compared on the criteria of the time taken for arc to reach to the diffuse state.

Keywords

References

  1. 하덕용, 강형부, 최승길, 최경호, '종자계형 진공 인터럽터에서 접점전극 슬릿의 영향에 관한 연구', 전기전자재료학회논문지, 15권, 9호, p. 822, 2002 https://doi.org/10.4313/JKEM.2002.15.9.822
  2. 하성철, 서상현, '축자계형 진공인터럽터의 전자계 현상 해석', 전기전자재료학회논문지, 16권, 10호, p. 952, 2003 https://doi.org/10.4313/JKEM.2003.16.10.952
  3. P. G. Slade, 'The vacuum interrupter: theory', Design and Application, Chapter 2, p. 163, 2007
  4. V. Lanen, 'The current interruption process in vacuum: analysis of the current and voltages of current-zero measurements', Doctoral thesis of Delft university of technology, Chapter 2, p. 7, 2008
  5. V. Lanen, 'The current interruption process in vacuum: analysis of the currents and voltage of current-zero measurements', The post arc current and the recovery voltage, p. 14, 2008
  6. P. G. Slade, The vacuum interrupter: Theory, Design, and Application, Chapter 4, p. 282, 2007
  7. E. Dullni, E. Schade, and W. Shang, 'Vacuum arcs driven by cross-magnetic fields(RMF)', IEEE Trans, on plasma science, Vol. 31, No. 5, p. 902, 2003 https://doi.org/10.1109/TPS.2003.818445
  8. J. Li, and W Jimei, 'Measurement and study of arc characteristics of vacuum interrupter with high voltage and high capacity', IEEE, XVIIth ISDEIV, p. 266, 1996
  9. M. B. Schulman, 'The Behavior of vacuum arcs between spiral contacts with a fixed- polarity arc shield', IEEE Trans on plasma science, Vol. 27, No. 4, p. 984, 1999 https://doi.org/10.1109/27.782270
  10. M. B. Schulman, 'Separation of spiral contacts and the motion of vacuum arcs at high AC currents', IEEE Trans. on plasma science, Vol. 21, No. 5, p. 484, 1993 https://doi.org/10.1109/27.249631
  11. S. Yanabu and E Kaneko, 'Research and development of axial magnetic field electrode and its application', IEEE, 18th ISDEIV, p. 1, 1998
  12. L. Zhiyuan, W. Jimei, W. Zheng, H. Yong, X. Jun, and G. Hang, 'Vacuum interrupter with cup-type electrode simulations of 3D axial magnetic field and eddy current in the contact', IEEE 19th ISDEIV, p. 459, 2000
  13. Y. Niwa, K. Sasage, K. Yokokura, and E. kaneko, 'The arc behavior and the interruption ability of the transversal magnetic field electrode in the vacuum interrupter', XXIInd ISDEIV, p. 161, 2006
  14. 박덕규, '플라즈마 및 핵융합물리학', 형설출판사, p. 197, 1985
  15. P. G. Slade, 'The vacuum interrupter: Theory', Design, and Application, Chapter 2, p. 158, 2007
  16. E. Dullni, 'Motion of high-current vacuum arcs on spiral type contacts', IEEE, Trans on plasma science, Vol. 17, No. 6, p. 875, 1989 https://doi.org/10.1109/27.41226