Evaporation Heat Transfer and Pressure Drop of Mixture Refrigerant R-22 and R-407C in a Diameter of 4.3 mm

4.3 mm 세관내 R-22와 R-407C의 증발 열전달과 압력강하

  • 노건상 (동명대학교 냉동공조공학과) ;
  • 손창효 (부경대학교 기계공학부 누리사업단)
  • Published : 2008.08.30

Abstract

The evaporation heat transfer coefficient and pressure drop of R-22 and R-407C in a small diameter copper tube were investigated experimentally. The main components of the refrigerant loop are a receiver, a compressor, a mass flow mete, a condense and a double pipe type evaporate (test section). The test section consists of a smooth copper tube of 4.3 mm inner diameter. The refrigerant mass fluxes were varied from 100 to $300[kg/m^{2}s]$ and the saturation temperature of evaporator were $5[^{\circ}C]$. The evaporation heat transfer coefficients of R-22 and R-407C increase with the Increase in mass flux and vapor quality. The evaporation heat transfer coefficient of R-22 is about $7.3\sim47.1%$ higher than that of R-407C. The evaporation pressure drop of R-22 and R-407C increase with the increase of mass flux. The pressure drop of R-22 is about $8\sim20%$ higher than that of R-407C.