Abstract
As the penetration of distributed generation systems is recently high, there have been metering errors, trips of protective devices in KEPCO distribution systems including an occurrence of false fault-indicator in distribution automation system. The cause of malfunctions was the reverse-power-flow phenomenon due to transformer wiring types. By the effect of the reverse-power-flow, each of phase's fundamental currents was added by about 3 times on the neutral line. A new method based on the analysis of the reverse-power-flow is proposed in this paper. Fault currents on each section were analyzed by the proposed method, and the effect of types of transformer wiring was examined experimentally. In order to reduce the malfunctions due to the reverse-power-flow, controlling the zero-sequence impedance of transformer was designed and verified by using PSCAD/EMTDC software.
본 논문에서는 최근 분산전원 확대보급에 따라 계량오차 발생, 변전소 CB 또는 Recloser, 수전설비 VCB의 OCGR 오동작, 배전자동화 시스템 거짓FI 정보발생 등 한전 배전계통에서 발생되는 오동작 현상에 대해서 원인분석을 수행하였고 그 원인은 변압기 결선에 의한 역 조류현상임을 규명하였다. 이러한 역 조류현상의 영향으로 배전계통의 3상 기본파 전류가 N상에서 동상이 되어 3배의 전류로 합산되었으며, 이 현상을 근거로 새로운 계통해석 방법을 제시하였다. 새로운 계통해석 방법을 적용하여 구간별 고장전류를 해석하였고, 역 조류현상 규명을 위해 변압기 결선형태 별로 역 조류 발생여부를 실험하였다. 또한 PSCAD/EMTDC로 실제 계통을 모의함으로써 역 조류에 의한 오동작 현상을 줄이기 위한 방법으로 중성선의 영상임피던스를 조절하는 방법을 제시하였다.