DOI QR코드

DOI QR Code

Make-up of Equivalent Circuit of Grounding System using Water Resistivity in Hemispherical Electrode System

반구형 전극계에서 물의 저항률을 이용한 접지시스템의 등가회로 구성

  • 이복희 (인하대학교 공대 전자전기공학부) ;
  • 최종혁 (인하대학교 공대 전자공학과 대학원) ;
  • 배성배 (인하대학교 정보전기공학과)
  • Published : 2008.08.31

Abstract

A design criterion of grounding systems is commonly based on the ground resistance measured with low frequency in Korea. When lightning surges which have high frequency components are injected into the grounding system, the grounding impedance is great]y different from the static grounding resistance. In order to investigate the effect of water resistivity on the high frequency performance of grounding systems, this paper presents the frequency-dependent admittance using water tank simulating the grounding system in different water resistivities. As a result, because of capacitive effect admittances and conductance are increased with increasing frequency in higher water resistivity of greater than 500[${\Omega}{\cdot}m$]. On the other hand, admittances and conductances are decreased with increasing frequency due to inductive effect in lower water resistivity of less than 500[${\Omega}{\cdot}m$]. The phase difference between the current and voltage increases in the range of 200[kHz] to 5[MHz]. Consequently, frequency-dependent performance of grounding systems is closely related to the soil resistivity, it is necessary to consider the effect of grounding system performance on the frequency and soil resistivity.

현재 우리나라의 접지시스템의 설계기준은 낮은 주파수에서 측정된 저항값을 기반으로 한다. 고주파 성분을 포함하는 뇌서지가 접지시스템에 인가되면, 접지임피던스는 정상상태의 저항과 매우 다르게 된다. 이 논문은 접지시스템의 고주파 성능에 대한 물의 저항률의 영향을 파악하기 위하여 대지를 모의하는 수조를 이용하여 물의 저항률에 따른 어드미턴스의 주파수 의존성을 기술하였다. 500[${\Omega}{\cdot}m$] 이상의 높은 물의 저항률에서 용량성 효과에 의해 주파수가 증가함에 따라 어드미턴스와 컨덕턴스가 증가하는 것으로 나타났다. 반면에, 500[${\Omega}{\cdot}m$] 미만의 낮은 저항률에서는 유도성 효과에 의해 주파수가 증가함에 따라 어드미턴스와 컨덕턴스가 감소하는 것으로 나타났다. 또한 200[kHz]에서 5[MHz]에 이르는 주파수 범위에서 전류와 전압의 위상차가 증가하는 것으로 나타났다. 결론적으로, 접지시스템의 주파수 의존성은 대지의 저항률과 밀접한 관계가 있으며, 주파수와 대지저항률이 접지시스템의 성능에 미치는 영향에 대한 고려가 필요하다.

Keywords

References

  1. R. Kosztaluk, M. Loboda, D. Mukhedkar, 'Experimental Study of Transient Ground Impedances', IEEE Trans. PAS, Vol.100, No.11, pp.4653-4660,1981
  2. T. Takahashi, T. Kawase, 'Calculation of Earth Resistance for a Deep-driven rod in Multi-layer Earth Structure', IEEE Trans. on PD, Vol.6, No.2, pp.608-614, 1991
  3. 이복희, 이승칠, '접지의 핵심 기호 기술', 의제, pp.40- 44, 1999
  4. J. Laot, 'Generation and Measurement of Fast Transient Overvoltages with Special Reference to Disconnector Operation in GIS', GIGRE, No. 33-86, 1986
  5. N. Mohamad Nor, 'Characteristics of sodium chloride (NaCl) under DC, AC and impulse conditions', 8th International Conference on Properties and Applications of Dielectric Materials, pp.926-931, 2006
  6. J. B. Rakov, M. A. Uman, M. I. Fernandez, C. T. Mata, K.J. Rambo, M. V. Stapleton, and R. R. Sutil, 'Direct lightning strikes to the lightning protective system of a residential building: triggered lighting experiments', IEEE Trans. on PD, Vol.17, No.2, pp.575-586, 2002
  7. R. Cadecott, D.G. Kasten, 'Scale Model Studies of Station Grounding Grids', IEEE Trans. PAS., Vol.102, No.3, pp.558-566, 1975
  8. F. Dawalibi, D. Mukedkar, 'Optimum Design of Substation Grounding in a Earth Structure : Part I-Analytical Study', IEEE Trans. PAS., Vol.94, No.2, pp.252-261, 1975 https://doi.org/10.1109/T-PAS.1975.31849
  9. Pedro Llovera, Juan Antonio LLiso, Alfredo Quijano, Vicente Fuster, 'High frequency measurements of grounding impedance on resistive soils', Proc. 28th ICLP, Vol.1, pp.727-729, 2006
  10. M. Irfan Jambak, Hussein Ahmad, 'Measurement of grounding system resistance based on ground high frequency behavior for different soil type', IEEE, Tencon 2000. Proc., Vol.3, pp.207-211, 2000
  11. M. A. Abdallah, 'High frequency performance of an earthing system', Proc. 13th ISH, pp.201-205, 2003
  12. 이복희, 이동문, 엄주홍, 김교운, '접지그리드의 접지임피던스의 주파수 위존성', 조명전기설비학회 논문지, Vol.17, No.5, pp.22-28, 2003
  13. Ju-Hong Eom, Sung-Chul Cho, Tae-Hyeong Lee and Bok-Hee Lee, 'Ground Impedance Analyzer using the Variable Frequency Wave Generator and PC Based Measuring System', Proc. 15th ISH, T2-475, pp.1-6, 2007