제트 환기 시스템 도입에 의한 플랜트 기자재 용접장의 환경 개선 효과 분석

Environmental Improvement in a Welding Factory by the Jet Ventilation System

  • 임정호 (한양대학교 대학원 플랜트엔지니어링공학과) ;
  • 이태구 (한양대학교 대학원 기계공학과) ;
  • 문승재 (한양대학교 기계공학부) ;
  • 이재헌 (한양대학교 대학원 플랜트엔지니어링공학과)
  • Lim, Jung-Ho (Department of Plant Engineering, Graduate School of Hanyang University) ;
  • Lee, Tae-Gu (Department of Mechanical Engineering, Graduate School of Hanyang University) ;
  • Moon, Seung-Jae (School of Mechanical Engineering, Hanyang University) ;
  • Lee, Jae-Heon (Department of Plant Engineering, Graduate School of Hanyang University)
  • 투고 : 2008.01.11
  • 심사 : 2008.06.10
  • 발행 : 2008.06.30

초록

In this inquiry, I would suggest jet ventilation system for effective elimination of welding flaw at machinery material welding shop on plant and evaluate the airstream on inner space and property of welding flaw's density through the examination. We can know outer atmosphere inflows at the speed of about 0.05m/s from western entrance in case of stopping the jet ventilation system, but airstream is accumulated on entire space. At height of worker's breathing surface(Ground Level = 1.5 m, below of GL) and welding work center, density of welding flaw on upper part(GL = 12m) is appeared 4 times higher than outer atmosphere at surplus range besides nearby of western entrance. At operation of jet ventilation system, since the smooth air current transfer at inner space and exhaust effect the wind speed is maintained at 0.932 m/s at the point of height of worker's breathing surface on inner space and it's concluded about the working conditions have been better than before operation of jet ventilation system because of that results show that inner space density of welding flaw at height of worker's breathing surface is 40.5%, and in the work shop, it is 20.3% at upper part.

키워드